Rule · CMS calculator
Space factor
publishedcms.rule.spaceFactor
How much of a closed section the cables may fill. The rest is the room that lets them be drawn in without damage and lets the heat out.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Containment | Space factor % | State |
|---|---|---|
| Trunking | 45 | |
| Duct | 35 | |
| Tray | 100 | |
| Ladder | 100 | |
| Basket | 100 |
5 rows
How the calculator uses it
The area check multiplies a size's area by it — in trunking and duct, and on open containment when the cables are piled (the Grouped layout), where the factor is the whole section. Open containment laid in a single layer is measured across its width instead, by the width check, and takes no space factor. The figure is stated per run and can be changed — a blank one is not stated, and the run asks for it rather than assuming.
Worked through on A trunking run — 12 × LSOH 1c 6mm², 6 × LSOH 1c 10mm², 4 × LSOH 1c 16mm²
| The size the engine chose | 50 × 50 mm |
|---|---|
| Its net internal area | 2,304.44 mm² |
| × the 45 % space factor × (1 − 30 % future spare) | 725.9 mm² usable |
| What the cables need | 693.4 mm² |
| Verdict | PASS — 95.5 % of the usable area |
Computed by the calculator for this run when this page was generated — not typed.
VERIFY before issue
Space factor (45% trunking / 35% duct) follows IET Guidance Note 1 Amd 3 Appendix A. Confirm the applicable limit for your installation and any project derating.
spaceFactor — the calculator’s own words, not a copy