Check · CMS calculator

Fill by width

published

cms.check.fillWidth

The sizing check for cables laid in a single layer on tray, ladder or basket: the width they take against the usable width.

Local graph

Leans on · 7Leaned on by · 1Cable catalogue — fed by, estimatedCable cataloguefed byLadder widths and usable sections — fed by, publishedLadder widths and usablesectionsfed byTray sizes — fed by, publishedTray sizesfed byWire basket sections — fed by, publishedWire basket sectionsfed byFuture spare — fed by, a choiceFuture sparefed byLayout spacing — fed by, publishedLayout spacingfed byThe no-clash rule for cleats — fed by, publishedThe no-clash rule for cleatsfed byCable Containment Capacity Calculator — feeds, estimatedCable ContainmentCapacity CalculatorfeedsFill by width Leans on · 7Leaned on by · 1Cable catalogue — fed by, estimatedCable cataloguefed byLadder widths and usable sections — fed by, publishedLadder widths andusable sectionsfed byTray sizes — fed by, publishedTray sizesfed byWire basket sections — fed by, publishedWire basketsectionsfed byFuture spare — fed by, a choiceFuture sparefed byLayout spacing — fed by, publishedLayout spacingfed byThe no-clash rule for cleats — fed by, publishedThe no-clash rulefor cleatsfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsFill by width Leans on · 7Leaned on by · 1Cable catalogue — fed by, estimatedCablecataloguefed byLadder widths and usable sections — fed by, publishedLadder widthsand usablesectionsfed byTray sizes — fed by, publishedTray sizesfed byWire basket sections — fed by, publishedWire basketsectionsfed byFuture spare — fed by, a choiceFuture sparefed byLayout spacing — fed by, publishedLayout spacingfed byThe no-clash rule for cleats — fed by, publishedThe no-clashrule for cleatsfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsFill by width

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

The width is each cable's diameter times its layout spacing — or, on a cleated run, its cleats laid by the no-clash rule — and the usable width is the inside width less the future spare.

Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung

The size the engine chose600 mm wide
Its inside width596 mm
Usable, with 30 % kept clear417.2 mm
What the cleats and cables take368.0 mm
VerdictPASS

Computed by the calculator for this run when this page was generated — not typed.