The no-clash rule for cleats
publishedcms.rule.noClash
How close two cleats, or a cleat and a cable, may stand across a rung. Two bodies on the same rung need a full body each; on different rungs, half of each plus half the other's cable; a body against a loose cable, half and half; two loose cables, half a diameter each — and any clearance you set, wherever a body is involved.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
It is ONE function. Laying out a cleated run, dragging a cleat in the rung editor and lining the cleats up with the slots all obey it, so the plan, the Section, the At a rung view and the 3-D cannot disagree. Nothing may stand past the future-spare line.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung
| The size the engine chose | 600 mm wide |
|---|---|
| Its inside width | 596 mm |
| Usable, with 30 % kept clear | 417.2 mm |
| What the cleats and cables take | 368.0 mm |
| Verdict | PASS |
Computed by the calculator for this run when this page was generated — not typed.