Table we keep · CMS calculator
Trunking net internal areas
publishedcms.table.trunkingAreas
The usable cross-section of each trunking size, before the space factor is applied and before the future spare is set aside.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
Not reproduced. The calculator holds these figures, derived from IET Guidance Note 1, Appendix A, which is cited only. Only the values a real calculation used are shown, in the worked example below.
How the calculator uses it
The area the cables may fill is this, times the space factor, times what is left after the future spare — and the area check compares the cables' areas with it.
Worked through on A trunking run — 12 × LSOH 1c 6mm², 6 × LSOH 1c 10mm², 4 × LSOH 1c 16mm²
| The size the engine chose | 50 × 50 mm |
|---|---|
| Its net internal area | 2,304.44 mm² |
| × the 45 % space factor × (1 − 30 % future spare) | 725.9 mm² usable |
| What the cables need | 693.4 mm² |
| Verdict | PASS — 95.5 % of the usable area |
Computed by the calculator for this run when this page was generated — not typed.
VERIFY before issue
Trunking net internal areas are derived from GN1 Amd 3 Appendix A (Table A6) — verify against the specified trunking manufacturer.
trunkingArea — the calculator’s own words, not a copy