Table we keep · CMS calculator
Cleat short-circuit declarations
publishedcms.table.cleatDeclarations
What each cleat range has survived, and under which conditions, as the maker publishes it.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
Two-Bolt LSF Nylon Cleats · 2
| Tested part | Current kA | Cleat spacing mm | Cable Ø mm | Phase spacing mm | Report | State |
|---|---|---|---|---|---|---|
| 2F+07LSF | 80.2 | 600 | 36 | 100 | PDL-17.137.3 | |
| 2F+142LSF | 113.0 | 1,000 | 117 | 200 | PDL-15.025.1 |
Single-Bolt LSF Nylon Cleats · 1
| Tested part | Current kA | Cleat spacing mm | Cable Ø mm | Phase spacing mm | Report | State |
|---|---|---|---|---|---|---|
| 1F (LSF) | 10.4 | 300 | 36 | 100 | PDL-17.137.2 |
Two-Bolt Aluminium Cleats (2A) · 2
| Tested part | Current kA | Cleat spacing mm | Cable Ø mm | Phase spacing mm | Report | State |
|---|---|---|---|---|---|---|
| — | 183.0 | 300 | 36 | 100 | PDL-18.071.1 | |
| — | 113.0 | 600 | 117 | 200 | PDL-15.025.1 |
5 rows · read live from tools/cleats/products.js shortCircuitDeclaration
How the calculator uses it
The cleat check reports the job's fault current against the lowest of these as a bound on the duty — read as a peak, the conservative reading — and says plainly that it is not a spacing selection and not a pass. A range printed untested can reach no short-circuit verdict at any spacing.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it
| Cleat | 2LSF07 — Two-Bolt LSF Nylon Cleats |
|---|---|
| Cable checked | A1 — XLPE/SWA/LSOH 4c 95mm² |
| Formation | Multi-core 3C/4C/5C — K = 0.17 (set from the cables) |
| Conductor spacing S | 13.2 mm |
| S, made up | 11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724 |
| Peak short-circuit current | 20.0 kA peak |
| Force per metre | 5152 N/m |
| F′ in the formula’s units | 0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres) |
| Cleat spacing used | 300 mm |
| Force per cleat | 1546 N |
| Design force (Fₜ × FoS) | 1546 N |
| Rated withstand | 10000 N — typed |
| Maximum spacing | 1941 mm |
| Recommended spacing | 1800 mm |
| Verdict | PASS |
The rows of the calculation sheet the calculator prints for this run — not typed.
VERIFY before issue
The two-bolt range declares 80.2 kA at 600 mm intervals (2F+07LSF) and 113 kA at 1 m (2F+142LSF), each with its cable and phase spacing (DS20E issue 04). Each is a bound on the duty survived under those conditions, not a spacing selection; the range is checked against the lower.
cleatProducts.boundNotSelection — the calculator’s own words, not a copy
The single-bolt range (10.0-57.0 mm, where most of the cable catalogue sits) was printed UNTESTED in the catalogue extract; DS33E issue 02 tests its LSF version to 10.4 kA at 300 mm intervals. The calculator still proposes two-bolt cleats only (Sparkline’s rule).
cleatProducts.untestedRange — the calculator’s own words, not a copy
NO RATED TENSILE STRENGTH (Fr) IS PUBLISHED IN THIS EXTRACT. The lateral-load, axial-movement and safe-working-load figures are different quantities and must never be entered as Fr. Fr comes from the product test certificate.
cleatProducts.noFr — the calculator’s own words, not a copy
The 45,239 N in the manufacturer’s calculator report (PDL10.204.2) is not on the data sheet and is not entered as Fr.
cleatProducts.aluminium.frNote — the calculator’s own words, not a copy