Check · CMS calculator

Cable cleat check

estimated

cms.check.cleatCheck

The cable cleat check: the maximum spacing of cleats for the run's fault current, and whether the run as laid is inside it.

Local graph

Leans on · 5Leaned on by · 1Cleat catalogue — fed by, publishedCleat cataloguefed byCleat short-circuit declarations — fed by, publishedCleat short-circuitdeclarationsfed byRung and slot geometry — fed by · the rung pitch, estimatedRung and slot geometryfed by · the rung pitchThe force on a cleat — fed by, estimatedThe force on a cleatfed byPower cables only — fed by, a choicePower cables onlyfed byCable Containment Capacity Calculator — feeds, estimatedCable ContainmentCapacity CalculatorfeedsCable cleat check Leans on · 5Leaned on by · 1Cleat catalogue — fed by, publishedCleat cataloguefed byCleat short-circuit declarations — fed by, publishedCleat short-circuitdeclarationsfed byRung and slot geometry — fed by · the rung pitch, estimatedRung and slotgeometryfed by · the rungpitchThe force on a cleat — fed by, estimatedThe force on acleatfed byPower cables only — fed by, a choicePower cables onlyfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsCable cleatcheck Leans on · 5Leaned on by · 1Cleat catalogue — fed by, publishedCleat cataloguefed byCleat short-circuit declarations — fed by, publishedCleatshort-circuitdeclarationsfed byRung and slot geometry — fed by · the rung pitch, estimatedRung and slotgeometryfed by · the rungpitchThe force on a cleat — fed by, estimatedThe force on acleatfed byPower cables only — fed by, a choicePower cablesonlyfed byCable Containment Capacity Calculator — feeds, estimatedCableContainmentCapacityCalculatorfeedsCable cleat check

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

How the calculator uses it

It checks the most onerous power cable a cleat covers — the one that sees the most force — and gives its own PASS or FAIL beside the containment's. Where no cleat fits a power cable, it still works out the force and says what a restraint at every rung must withstand, by its declared short-circuit rating.

Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it

Cleat2LSF07 — Two-Bolt LSF Nylon Cleats
Cable checkedA1 — XLPE/SWA/LSOH 4c 95mm²
FormationMulti-core 3C/4C/5C — K = 0.17 (set from the cables)
Conductor spacing S13.2 mm
S, made up11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724
Peak short-circuit current20.0 kA peak
Force per metre5152 N/m
F′ in the formula’s units0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres)
Cleat spacing used300 mm
Force per cleat1546 N
Design force (Fₜ × FoS)1546 N
Rated withstand10000 N — typed
Maximum spacing1941 mm
Recommended spacing1800 mm
VerdictPASS

The rows of the calculation sheet the calculator prints for this run — not typed.

VERIFY before issue

NO RATED TENSILE STRENGTH (Fr) IS PUBLISHED IN THIS EXTRACT. The lateral-load, axial-movement and safe-working-load figures are different quantities and must never be entered as Fr. Fr comes from the product test certificate.

cleatProducts.noFr — the calculator’s own words, not a copy

The two-bolt range declares 80.2 kA at 600 mm intervals (2F+07LSF) and 113 kA at 1 m (2F+142LSF), each with its cable and phase spacing (DS20E issue 04). Each is a bound on the duty survived under those conditions, not a spacing selection; the range is checked against the lower.

cleatProducts.boundNotSelection — the calculator’s own words, not a copy

A stagger onto alternate rungs relaxes the same-rung clearance and NOT the clearance to the neighbouring cable. Below the neighbour minimum there is no arrangement at any number of rungs.

cleatEngine.4 — the calculator’s own words, not a copy