Check · CMS calculator
Cable cleat check
estimatedcms.check.cleatCheck
The cable cleat check: the maximum spacing of cleats for the run's fault current, and whether the run as laid is inside it.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
It checks the most onerous power cable a cleat covers — the one that sees the most force — and gives its own PASS or FAIL beside the containment's. Where no cleat fits a power cable, it still works out the force and says what a restraint at every rung must withstand, by its declared short-circuit rating.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it
| Cleat | 2LSF07 — Two-Bolt LSF Nylon Cleats |
|---|---|
| Cable checked | A1 — XLPE/SWA/LSOH 4c 95mm² |
| Formation | Multi-core 3C/4C/5C — K = 0.17 (set from the cables) |
| Conductor spacing S | 13.2 mm |
| S, made up | 11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724 |
| Peak short-circuit current | 20.0 kA peak |
| Force per metre | 5152 N/m |
| F′ in the formula’s units | 0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres) |
| Cleat spacing used | 300 mm |
| Force per cleat | 1546 N |
| Design force (Fₜ × FoS) | 1546 N |
| Rated withstand | 10000 N — typed |
| Maximum spacing | 1941 mm |
| Recommended spacing | 1800 mm |
| Verdict | PASS |
The rows of the calculation sheet the calculator prints for this run — not typed.
VERIFY before issue
NO RATED TENSILE STRENGTH (Fr) IS PUBLISHED IN THIS EXTRACT. The lateral-load, axial-movement and safe-working-load figures are different quantities and must never be entered as Fr. Fr comes from the product test certificate.
cleatProducts.noFr — the calculator’s own words, not a copy
The two-bolt range declares 80.2 kA at 600 mm intervals (2F+07LSF) and 113 kA at 1 m (2F+142LSF), each with its cable and phase spacing (DS20E issue 04). Each is a bound on the duty survived under those conditions, not a spacing selection; the range is checked against the lower.
cleatProducts.boundNotSelection — the calculator’s own words, not a copy
A stagger onto alternate rungs relaxes the same-rung clearance and NOT the clearance to the neighbouring cable. Below the neighbour minimum there is no arrangement at any number of rungs.
cleatEngine.4 — the calculator’s own words, not a copy