Rule · CMS calculator
Power cables only
a choicecms.rule.powerOnly
Only cables that can carry the run's fault current are force-checked. A cable of more cores is a control cable — taken not to carry it — and is left out and named.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Setting | Cores | State |
|---|---|---|
| Most cores in a power cable | 5 |
1 row
How the calculator uses it
Without it, a many-core control cable — its cores a few millimetres apart — carried the most force on a power ladder and failed runs its power cables pass. A row you name is checked whatever it is.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it
| Cleat | 2LSF07 — Two-Bolt LSF Nylon Cleats |
|---|---|
| Cable checked | A1 — XLPE/SWA/LSOH 4c 95mm² |
| Formation | Multi-core 3C/4C/5C — K = 0.17 (set from the cables) |
| Conductor spacing S | 13.2 mm |
| S, made up | 11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724 |
| Peak short-circuit current | 20.0 kA peak |
| Force per metre | 5152 N/m |
| F′ in the formula’s units | 0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres) |
| Cleat spacing used | 300 mm |
| Force per cleat | 1546 N |
| Design force (Fₜ × FoS) | 1546 N |
| Rated withstand | 10000 N — typed |
| Maximum spacing | 1941 mm |
| Recommended spacing | 1800 mm |
| Verdict | PASS |
The rows of the calculation sheet the calculator prints for this run — not typed.