Rule · CMS calculator
The force on a cleat
estimatedcms.rule.cleatForce
The force a fault puts between the conductors, per metre of cable, and so on each cleat holding them.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
How the calculator uses it
F′ = K × Iₚₖ² ÷ S · Fₜ = F′ × spacing · Lₘₐₓ = Fᵣ ÷ (F′ × FoS)
Units. F′ comes out in N/m when Iₚₖ is in kA and S in metres: K carries the units (N/kA²). The sheet prints S in millimetres, so divide it by 1,000 first. Fₜ and Fᵣ are in newtons; the spacing and Lₘₐₓ are in metres.
The force per metre is K times the square of the peak current, divided by the spacing between the conductors — in newtons per metre when the current is in kiloamps and the spacing in metres, the units K is given in. Each cleat holds one gap's length of it. The check takes the cleat's rated withstand, divided by the factor of safety, as what one cleat may carry — so the longest gap is that, divided by the force per metre — and on a ladder rounds it DOWN to whole rungs. For a multicore cable the spacing is the estimated core pair, not the cable's outside diameter.
Watch for
It is a conservative design check: it takes every gap as equal and an estimated core spacing. Verify the rating with the cleat's maker before issue.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it
| Cleat | 2LSF07 — Two-Bolt LSF Nylon Cleats |
|---|---|
| Cable checked | A1 — XLPE/SWA/LSOH 4c 95mm² |
| Formation | Multi-core 3C/4C/5C — K = 0.17 (set from the cables) |
| Conductor spacing S | 13.2 mm |
| S, made up | 11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724 |
| Peak short-circuit current | 20.0 kA peak |
| Force per metre | 5152 N/m |
| F′ in the formula’s units | 0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres) |
| Cleat spacing used | 300 mm |
| Force per cleat | 1546 N |
| Design force (Fₜ × FoS) | 1546 N |
| Rated withstand | 10000 N — typed |
| Maximum spacing | 1941 mm |
| Recommended spacing | 1800 mm |
| Verdict | PASS |
The rows of the calculation sheet the calculator prints for this run — not typed.
VERIFY before issue
S FOR A MULTI-CORE CABLE IS THE ADJACENT CORE PAIR, NOT THE CABLE'S OUTSIDE DIAMETER. S = (d + 2t) with d = 2·√(A/π), transcribed from Sparkline's Cable Cleat Calculator v3 (Cable Data sheet). The solid-round d under-states a stranded conductor, which over-states the force — an assumption that can only make the answer worse.
coreGeometry.method — the calculator’s own words, not a copy