Constant · CMS calculator

Insulation thickness

estimated

cms.constant.insulationThickness

The insulation on one conductor, by conductor size. It sets how far apart the cores of a multicore cable sit — and the force between them goes as one over that spacing.

Local graph

Leans on · 3Leaned on by · 1Cable cleat calculation workbook — transcribes, publishedCable cleat calculationworkbooktranscribesBS 5467 / BS 6724 — named by, publishedBS 5467 / BS 6724named bySparkline’s project cable data — derived from, estimatedSparkline’s project cabledataderived fromThe force on a cleat — feeds, estimatedThe force on a cleatfeedsInsulation thickness Leans on · 3Leaned on by · 1Cable cleat calculation workbook — transcribes, publishedCable cleatcalculationworkbooktranscribesBS 5467 / BS 6724 — named by, publishedBS 5467 / BS6724named bySparkline’s project cable data — derived from, estimatedSparkline’s projectcable dataderived fromThe force on a cleat — feeds, estimatedThe force on acleatfeedsInsulationthickness Leans on · 3Leaned on by · 1Cable cleat calculation workbook — transcribes, publishedCable cleatcalculationworkbooktranscribesBS 5467 / BS 6724 — named by, publishedBS 5467 / BS6724named bySparkline’s project cable data — derived from, estimatedSparkline’sproject cabledataderived fromThe force on a cleat — feeds, estimatedThe force on acleatfeedsInsulation thickness

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The table we actually use

Conductor mm²Insulation t mmFromState
6.00.7project data◐ estimated: project practice, not a standard
25.00.9project data◐ estimated: project practice, not a standard
50.01.0project data◐ estimated: project practice, not a standard
70.01.1project data◐ estimated: project practice, not a standard
150.01.8project data◐ estimated: disputed: one of three project rows whose thickness falls as the conductor grows — insulation does not thin, so one of them is wrong
185.01.6project data◐ estimated: disputed: one of three project rows whose thickness falls as the conductor grows — insulation does not thin, so one of them is wrong
240.01.7project data◐ estimated: disputed: one of three project rows whose thickness falls as the conductor grows — insulation does not thin, so one of them is wrong

7 rows · 7 marked estimated (hover the mark for why) · read live from tools/cleats/core-geometry.js INSULATION_T

12 more rows are withheld. The calculator holds them, but the workbook attributes them to BS 5467 / BS 6724, a BSI standard we cite only — a transcription does not make that table ours to publish. Only the value a real calculation used is shown, in the worked example below.

How the calculator uses it

The spacing between a multicore cable's cores is the conductor's diameter plus twice this thickness (the force on a cleat).

Only the rows from Sparkline's project data are shown. The rest the workbook attributes to the cable standards; the calculator uses them, but a BSI table is cited, never published, so the worked example shows only the one row a real run used.

Where the sources disagree

Insulation does not thin as a conductor grows — except in three rows here, all from project data, where it does. One of them is wrong, and it matters in one direction: a thickness too large gives a spacing too large and so a force too small. They are flagged, reported and left exactly as Sparkline's sheet has them — nothing is smoothed over.

Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it

Cleat2LSF07 — Two-Bolt LSF Nylon Cleats
Cable checkedA1 — XLPE/SWA/LSOH 4c 95mm²
FormationMulti-core 3C/4C/5C — K = 0.17 (set from the cables)
Conductor spacing S13.2 mm
S, made up11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724
Peak short-circuit current20.0 kA peak
Force per metre5152 N/m
F′ in the formula’s units0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres)
Cleat spacing used300 mm
Force per cleat1546 N
Design force (Fₜ × FoS)1546 N
Rated withstand10000 N — typed
Maximum spacing1941 mm
Recommended spacing1800 mm
VerdictPASS

The rows of the calculation sheet the calculator prints for this run — not typed.

Where the sources disagree

VERIFY before issue

INSULATION THICKNESS IS NOT ALL FROM ONE PLACE. Rows marked bs5467 come from a standard this repo does not hold; rows marked project are Sparkline's project cable data — practice, not a standard. Every row carries its own provenance. NOT INTERPOLATED — an untabulated size returns nothing.

coreGeometry.thickness — the calculator’s own words, not a copy

ONE ANOMALY, LEFT AS THE SOURCE HAS IT: t falls from 1.8 mm at 150 mm² to 1.6 mm at 185 mm² and 1.7 mm at 240 mm². Insulation does not thin as a conductor grows, so one of those three is wrong. All three are project-data rows. Confirm against the cable actually specified.

coreGeometry.anomaly — the calculator’s own words, not a copy