Constant · CMS calculator
Formation constants K
publishedcms.constant.kValues
The constant the force law takes for each way the conductors can lie — a multicore cable's cores, single cores in trefoil, flat, or a single-phase pair.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
| Formation | K | State |
|---|---|---|
| 1C × 3 trefoil (3-ph) | 0.17 | |
| 1C × 3 flat — outer (3-ph) | 0.17 | |
| 1C × 3 flat — middle (3-ph) | 0.20 | |
| 1C × 2 / single-phase | 0.20 | |
| Multi-core 3C/4C/5C | 0.17 |
5 rows · read live from tools/cleats/engine.js K_FORMATIONS
How the calculator uses it
The force on a cleat multiplies the square of the fault current by K. Where a run has no single cores, the formation is set by the cables and the check says so rather than offering a choice.
Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it
| Cleat | 2LSF07 — Two-Bolt LSF Nylon Cleats |
|---|---|
| Cable checked | A1 — XLPE/SWA/LSOH 4c 95mm² |
| Formation | Multi-core 3C/4C/5C — K = 0.17 (set from the cables) |
| Conductor spacing S | 13.2 mm |
| S, made up | 11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724 |
| Peak short-circuit current | 20.0 kA peak |
| Force per metre | 5152 N/m |
| F′ in the formula’s units | 0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres) |
| Cleat spacing used | 300 mm |
| Force per cleat | 1546 N |
| Design force (Fₜ × FoS) | 1546 N |
| Rated withstand | 10000 N — typed |
| Maximum spacing | 1941 mm |
| Recommended spacing | 1800 mm |
| Verdict | PASS |
The rows of the calculation sheet the calculator prints for this run — not typed.
VERIFY before issue
The coefficients K are transcribed from Sparkline's own cleat workbook, attributed there to IEC 61914 / BS EN 61914 Annex A. Neither standard is held locally; both are NAMED, never described.
cleatEngine.1 — the calculator’s own words, not a copy
K for a flat three-phase MIDDLE conductor is 0.20 here and √3/2 ≈ 0.173 in this site's own published cleat article — a 15.6 % gap. The conservative figure ships, and both are recorded.
cleatEngine.2 — the calculator’s own words, not a copy