Constant · CMS calculator

Formation constants K

published

cms.constant.kValues

The constant the force law takes for each way the conductors can lie — a multicore cable's cores, single cores in trefoil, flat, or a single-phase pair.

Local graph

Leans on · 1Leaned on by · 1Cable cleat calculation workbook — transcribes · IEC 61914 Annex A, as the workbook has it, publishedCable cleat calculationworkbooktranscribes · IEC 61914 AnnexA, as the workbook has itThe force on a cleat — feeds, estimatedThe force on a cleatfeedsFormation constants K Leans on · 1Leaned on by · 1Cable cleat calculation workbook — transcribes · IEC 61914 Annex A, as the workbook has it, publishedCable cleatcalculationworkbooktranscribes · IEC61914 Annex A, asthe workbook has itThe force on a cleat — feeds, estimatedThe force on acleatfeedsFormationconstants K Leans on · 1Leaned on by · 1Cable cleat calculation workbook — transcribes · IEC 61914 Annex A, as the workbook has it, publishedCable cleatcalculationworkbooktranscribes · IEC61914 Annex A,as the workbookhas itThe force on a cleat — feeds, estimatedThe force on acleatfeedsFormation constants K

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The table we actually use

FormationKState
1C × 3 trefoil (3-ph)0.17
1C × 3 flat — outer (3-ph)0.17
1C × 3 flat — middle (3-ph)0.20
1C × 2 / single-phase0.20
Multi-core 3C/4C/5C0.17

5 rows · read live from tools/cleats/engine.js K_FORMATIONS

How the calculator uses it

The force on a cleat multiplies the square of the fault current by K. Where a run has no single cores, the formation is set by the cables and the check says so rather than offering a choice.

Worked through on the owner’s ladder run — 4 × XLPE/SWA/LSOH 4c 95mm², cleated on every rung — the cleat working as the calculator prints it

Cleat2LSF07 — Two-Bolt LSF Nylon Cleats
Cable checkedA1 — XLPE/SWA/LSOH 4c 95mm²
FormationMulti-core 3C/4C/5C — K = 0.17 (set from the cables)
Conductor spacing S13.2 mm
S, made up11.0 mm conductor + 2 × 1.1 mm insulation = 13.2 mm — the insulation row this cable used, which the workbook attributes to BS 5467 / BS 6724
Peak short-circuit current20.0 kA peak
Force per metre5152 N/m
F′ in the formula’s units0.17 × 20.0² ÷ 0.013198 m = 5,152 N/m (Iₚₖ in kA, S in metres)
Cleat spacing used300 mm
Force per cleat1546 N
Design force (Fₜ × FoS)1546 N
Rated withstand10000 N — typed
Maximum spacing1941 mm
Recommended spacing1800 mm
VerdictPASS

The rows of the calculation sheet the calculator prints for this run — not typed.

VERIFY before issue

The coefficients K are transcribed from Sparkline's own cleat workbook, attributed there to IEC 61914 / BS EN 61914 Annex A. Neither standard is held locally; both are NAMED, never described.

cleatEngine.1 — the calculator’s own words, not a copy

K for a flat three-phase MIDDLE conductor is 0.20 here and √3/2 ≈ 0.173 in this site's own published cleat article — a 15.6 % gap. The conservative figure ships, and both are recorded.

cleatEngine.2 — the calculator’s own words, not a copy