Document · CMS calculator

2F+ two hole clamp — data sheet DS20E

published

cms.doc.ellisDs20e

The current Ellis data sheet for the 2F+ two-hole nylon clamp — the two-bolt range the calculator proposes. Page 1 is the dimension table; page 2 the testing summary, with two short-circuit tests and the conditions each was made under.

Local graph

Leans on · 0Leaned on by · 2NothingCleat catalogue — transcribed into · heights and bolts, publishedCleat cataloguetranscribed into · heights andboltsCleat short-circuit declarations — transcribed into · p.2, publishedCleat short-circuitdeclarationstranscribed into · p.22F+ two hole clamp —data sheet DS20E Leans on · 0Leaned on by · 2NothingCleat catalogue — transcribed into · heights and bolts, publishedCleat cataloguetranscribed into ·heights and boltsCleat short-circuit declarations — transcribed into · p.2, publishedCleat short-circuitdeclarationstranscribed into · p.22F+ two holeclamp — datasheet DS20E Leans on · 0Leaned on by · 2NothingCleat catalogue — transcribed into · heights and bolts, publishedCleat cataloguetranscribed into ·heights and boltsCleat short-circuit declarations — transcribed into · p.2, publishedCleatshort-circuitdeclarationstranscribed into ·p.22F+ two hole clamp — datasheet DS20E

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The original document

Publisher
Ellis Patents
Title
Data sheet DS20E “2F+ two hole clamp”
Edition
issue 04, 30/09/26
Where in it
p.1 the dimension table; p.2 the testing summary
Do we hold it
downloaded from the maker
May it be reproduced here
In small extracts, quoted with acknowledgement. The document is the authority.

Ellis Patents — 2F two-hole clamp ↗ We are not the source of record.

What the document says

Ellis DS20E issue 04 p.1: the column heads and four rows of the 2F+ range — 2F+07 and 2F+1200 to 2F+1202 — cable range, liner, width W, height H, depth D, fixing centres P and bolts
Quoted extract — the column heads and four sample rows, with the heights and bolts the calculator takes. From Ellis Patents, Data sheet DS20E “2F+ two hole clamp”, issue 04, 30/09/26, p.1. © Ellis Patents; quoted with acknowledgement for criticism and review — only the part that shows what the calculator takes, never a whole table. The document is the authority.
Ellis DS20E issue 04 p.2: two short-circuit tests, 80.2 kA and 113 kA, with their cleat spacing, cable diameter and phase spacing
Quoted extract — the two short-circuit tests and the conditions they were made under. From Ellis Patents, Data sheet DS20E “2F+ two hole clamp”, issue 04, 30/09/26, p.2. © Ellis Patents; quoted with acknowledgement for criticism and review — only the part that shows what the calculator takes, never a whole table. The document is the authority.

How the calculator uses it

The cleat catalogue takes every two-bolt part's HEIGHT and BOLTS from page 1, which is why the 1200, 1201 and 1202 parts are on M10 although the older catalogue printed M12. The declarations carry page 2's tests, read as peak currents — the conservative reading — and the lower one bounds the duty the check reports.

Watch for

A declaration is a duty the cleat survived at a stated spacing, cable and phase spacing — not a spacing selection, and not a pass.

Where the sources disagree