GN1's factor method for conduit: every cable has a factor, every conduit a factor, and the cables' factors must add up to no more than the conduit's — with different tables for a short straight run and for a longer run or one with bends.

Local graph

Leans on · 1Leaned on by · 1IET Guidance Note 1, Appendix A — transcribes · Tables A1–A4, publishedIET Guidance Note 1,Appendix Atranscribes · Tables A1–A4Conduit factors — feeds, publishedConduit factorsfeedsConduit and cablefactors Leans on · 1Leaned on by · 1IET Guidance Note 1, Appendix A — transcribes · Tables A1–A4, publishedIET Guidance Note1, Appendix Atranscribes · TablesA1–A4Conduit factors — feeds, publishedConduit factorsfeedsConduit andcable factors Leans on · 1Leaned on by · 1IET Guidance Note 1, Appendix A — transcribes · Tables A1–A4, publishedIET GuidanceNote 1,Appendix Atranscribes ·Tables A1–A4Conduit factors — feeds, publishedConduit factorsfeedsConduit and cable factors

publishedestimateda choiceno sourceArrows: the way the data flows

See it in the whole calculator

The table we actually use

Not reproduced. The calculator holds these figures, derived from IET Guidance Note 1, Appendix A, which is cited only. Only the values a real calculation used are shown, in the worked example below.

How the calculator uses it

The conduit check adds up the cable factors and finds the smallest conduit whose factor, less the future spare, covers them for the run's length and bends — so a conduit that would just take the cables today can be one size too small. The tables are IET copyright, so the page shows only the factors one real run used.

Watch for

A run's length and bends decide which tables apply — GN1 uses different ones for each. Where they have not been entered the calculator sizes on an assumed run and says so on the screen and the sheet, so enter the real one. Only single-core LSOH and PVC cables have a factor, so a rigid conduit run offers no other cable. Flexible and oval conduit are not in GN1's tables: they are sized by area, on the maker's inside areas and a distributor's oval sizes.

Worked through on A conduit run — 2.5 m straight, no bends, a 30 % future spare typed in (a conduit starts with none)

6 × LSOH 1c 2.5mm²cable factor 43 each, from Table A1
3 × LSOH 1c 4mm²cable factor 58 each, from Table A1
Their sum432
20 mm conduitfactor 460 × (1 − 30 % future spare) = 322 — too small for 432
25 mm conduitfactor 800 × (1 − 30 % future spare) = 560 — covers 432
The conduit the engine chose25 mm — the smallest whose factor, less the future spare, covers the cables (Table A2)
VerdictPASS

Computed by the calculator for this run when this page was generated — not typed. The factors shown are only the cells this run used.

VERIFY before issue

Conduit sizing uses the cable-factor / conduit-factor method of IET Guidance Note 1: Selection & Erection, Appendix A (Tables A1–A4), pp.134–136. It accounts for the ease of drawing the cables in, NOT the electrical effects of grouping — apply the grouping factor separately in the cable calculation. Confirm the factors against your own copy of GN1.

conduitFactor — the calculator’s own words, not a copy

Conduit bore diameters are indicative and vary by manufacturer and gauge. They are used only for the diagram and the bend-radius check, never for sizing — confirm against the product datasheet.

conduitBore — the calculator’s own words, not a copy

GN1 uses different cable factors below and above 3 m, and different again once a run has bends. Check that the run length and bend count recorded here match the installation.

conduitRegime — the calculator’s own words, not a copy

The run length and/or the number of bends were not entered, so this conduit is sized on an assumed run of 4 m with 2 bends (GN1 Tables A3/A4). Enter the real run: a longer run or more bends can need a bigger conduit.

conduitRunAssumed — the calculator’s own words, not a copy