Conduit and cable factors
publishedcms.table.conduitFactors
GN1's factor method for conduit: every cable has a factor, every conduit a factor, and the cables' factors must add up to no more than the conduit's — with different tables for a short straight run and for a longer run or one with bends.
Local graph
publishedestimateda choiceno sourceArrows: the way the data flows
The table we actually use
Not reproduced. The calculator holds these figures, derived from IET Guidance Note 1, Appendix A, which is cited only. Only the values a real calculation used are shown, in the worked example below.
How the calculator uses it
The conduit check adds up the cable factors and finds the smallest conduit whose factor, less the future spare, covers them for the run's length and bends — so a conduit that would just take the cables today can be one size too small. The tables are IET copyright, so the page shows only the factors one real run used.
Watch for
A run's length and bends decide which tables apply — GN1 uses different ones for each. Where they have not been entered the calculator sizes on an assumed run and says so on the screen and the sheet, so enter the real one. Only single-core LSOH and PVC cables have a factor, so a rigid conduit run offers no other cable. Flexible and oval conduit are not in GN1's tables: they are sized by area, on the maker's inside areas and a distributor's oval sizes.
Worked through on A conduit run — 2.5 m straight, no bends, a 30 % future spare typed in (a conduit starts with none)
| 6 × LSOH 1c 2.5mm² | cable factor 43 each, from Table A1 |
|---|---|
| 3 × LSOH 1c 4mm² | cable factor 58 each, from Table A1 |
| Their sum | 432 |
| 20 mm conduit | factor 460 × (1 − 30 % future spare) = 322 — too small for 432 |
| 25 mm conduit | factor 800 × (1 − 30 % future spare) = 560 — covers 432 |
| The conduit the engine chose | 25 mm — the smallest whose factor, less the future spare, covers the cables (Table A2) |
| Verdict | PASS |
Computed by the calculator for this run when this page was generated — not typed. The factors shown are only the cells this run used.
VERIFY before issue
Conduit sizing uses the cable-factor / conduit-factor method of IET Guidance Note 1: Selection & Erection, Appendix A (Tables A1–A4), pp.134–136. It accounts for the ease of drawing the cables in, NOT the electrical effects of grouping — apply the grouping factor separately in the cable calculation. Confirm the factors against your own copy of GN1.
conduitFactor — the calculator’s own words, not a copy
Conduit bore diameters are indicative and vary by manufacturer and gauge. They are used only for the diagram and the bend-radius check, never for sizing — confirm against the product datasheet.
conduitBore — the calculator’s own words, not a copy
GN1 uses different cable factors below and above 3 m, and different again once a run has bends. Check that the run length and bend count recorded here match the installation.
conduitRegime — the calculator’s own words, not a copy
The run length and/or the number of bends were not entered, so this conduit is sized on an assumed run of 4 m with 2 bends (GN1 Tables A3/A4). Enter the real run: a longer run or more bends can need a bigger conduit.
conduitRunAssumed — the calculator’s own words, not a copy