An RCD trips when it sees an imbalance between the current going out on the line and coming back
on the neutral — the "residual" current that must be leaking to earth. But not every RCD can
see every kind of leakage. As electronics, EV chargers and inverter-driven equipment
have spread, the type of RCD has become a design decision, not a default — and fitting the wrong
one can leave a circuit that looks protected but isn't.
The short version: Type A is the modern minimum. Step up to Type F for
inverter/variable-frequency loads, and Type B where smooth DC can occur (some EV charging,
three-phase drives, PV). The waveform the equipment leaks decides the type; the mA rating (30 mA
etc.) is a separate choice.
The Four Types
| Type | Detects | Typical use |
| AC | Sinusoidal AC only | Restricted — only fixed loads known to have no DC component |
| A | AC + pulsating DC (up to 6 mA smooth) | The general minimum — sockets, lighting, most circuits |
| F | Type A + mixed frequencies | Single-phase inverter / VFD loads — heat pumps, some appliances |
| B | All of the above + smooth DC | Three-phase drives, some EV charging, PV, medical |
Each type is a superset of the one before it: a Type B detects everything a Type A does, plus
more. The cost rises steeply from A to B, which is why you fit the lowest type that genuinely
covers the load rather than defaulting to B everywhere.
Why It Changed: DC Blinding
The move away from Type AC wasn't fashion. Modern equipment with rectifiers and switch-mode
power supplies can leak smooth DC to earth. That DC can magnetically saturate the core
of a Type AC RCD and stop it responding to a later AC fault — the device is still there, still
looks fine, but has been "blinded". A Type A tolerates pulsating DC and a small amount of smooth
DC; beyond that you need Type F or B. This is why the standard now restricts Type AC to a narrow
set of loads.
Choosing by Equipment
- General sockets and lighting: Type A.
- Washing machines, dishwashers, IT loads: Type A is normally sufficient.
- Heat pumps, air conditioning, inverter appliances: Type F or B — follow the manufacturer.
- EV charge points: Type A upstream if the charger provides its own 6 mA DC detection; otherwise Type B.
- Three-phase variable-speed drives, PV without isolation, medical: Type B.
Type Is Not the Same as Rating
Keep two ideas separate. The type (AC/A/F/B) is which waveforms it detects. The
rated residual current IΔn is the leakage at which it trips: 30 mA for
additional protection against shock (most socket outlets and outdoor mobile equipment), and
100 mA or 300 mA for fire protection and for achieving selectivity between RCDs. A
30 mA Type A and a 300 mA Type A are both "Type A" but do very different jobs.
Where This Fits
RCD selection sits alongside disconnection times, earth-fault loop impedance and
discrimination in the
protection design. On a TT
system an RCD is essential for automatic disconnection; on any system it's how you provide
additional shock protection. Getting the schedule of RCD types and ratings right, board by board,
is part of a coordinated protection design.
Frequently Asked Questions
What is the minimum RCD type for new installations?
Type A. BS 7671 now restricts Type AC to specific fixed equipment known to have no DC components, so for general new work — socket outlets and most circuits — Type A is the practical minimum, because it detects the pulsating DC leakage that modern electronic loads produce.
What RCD type does an EV charger need?
It depends on the charge point. If the EVSE has built-in protection against smooth (6 mA) DC fault current, a Type A RCD upstream is acceptable; if it does not, a Type B RCD is required, because a DC fault from the vehicle could otherwise blind an ordinary RCD. Always follow the charge-point manufacturer's instructions.
What RCD type does a heat pump need?
Heat pumps use variable-frequency (inverter) drives, which can produce mixed-frequency and smooth DC leakage. That usually calls for a Type F or Type B RCD depending on the drive — check the manufacturer's stated requirement rather than fitting a Type A by default.
Can a Type AC RCD be "blinded"?
Yes. Smooth DC leakage from electronic equipment can magnetically saturate a Type AC (or even Type A) RCD's core and stop it tripping on a subsequent AC fault — the "blinding" effect. This is the core reason the standard moved away from Type AC and introduced the higher types.
What is the difference between a 30 mA and a 100 mA RCD?
The rating (IΔn) is the residual current at which it trips, separate from the type. 30 mA is the level for additional protection against electric shock (required on most socket outlets and mobile equipment used outdoors); 100 mA and 300 mA devices are used for fire protection and for selectivity between RCDs, not for personal shock protection.
For the exact requirements, see BS 7671 Regulation 531.3.3 and the manufacturer's
instructions for the connected equipment.