Whether a circuit disconnects safely in a fault, what protective device you need, and how much
bonding the job requires all depend on one thing decided before you draw a single cable: the
earthing system. BS 7671 describes it with a short letter code — TN-S, TN-C-S, TT, IT — and
getting it right is the foundation of a safe design. Here's what each code means, how to tell
which you have, and why it matters.
The short version: the first letter says how the supply is earthed,
the second how your installation is earthed. TN-C-S (PME) is the common modern supply —
lowest loop impedance but an open-PEN risk; TN-S is separate earth throughout; TT is your own
electrode and needs an RCD.
The Naming Code
The letters come from IEC 60364 and read left to right:
- First letter — the supply's relationship to earth: T (terra) = one point (the transformer star point) is directly earthed; I = isolated or earthed through an impedance.
- Second letter — how your exposed metalwork is earthed: T = to your own local earth electrode; N = to the supply's earthed point via a supplied earth conductor.
- Further letters (S / C) — how neutral and earth are arranged in the supply: S = separate conductors; C = combined into one (PEN).
TN-S — Separate Earth Throughout
Neutral (N) and protective earth (PE) are separate conductors all the way from the transformer
to the installation. The earth path is traditionally the metallic sheath or armour of the
service cable. It gives a reliable, low-impedance earth and avoids the combined-conductor risk of
PME. Common on older urban supplies.
TN-C-S (PME) — Combined, Then Separated
The supply brings a single PEN (combined protective-earth-and-neutral)
conductor to the property, and it is split into separate N and PE at the origin. This is
Protective Multiple Earthing (PME), the standard modern UK arrangement. It usually has the lowest
external loop impedance (Ze), so faults clear fast — but it carries the open-PEN
risk: if the combined conductor breaks out in the network, the installation's earthed
metalwork can rise toward mains voltage. That single risk drives the strict main-bonding
requirements on PME supplies, and the special rules for outdoor EV charging.
TT — Your Own Earth Electrode
The DNO provides no earth; the installation makes its own connection to earth with a local
electrode (usually one or more rods). Common in rural areas and where the supply is overhead.
Because an electrode's resistance is high compared with a metallic supply earth, the earth-fault
loop impedance is high — too high for an overcurrent device to disconnect in time — so a
TT system needs an RCD for automatic disconnection, sized so that
Ra × IΔn ≤ 50 V.
IT — Rare in the UK
The supply is unearthed or earthed only through a high impedance, and exposed metalwork is
earthed locally. A first fault doesn't cause a large fault current, so supply continuity is
maintained and an alarm is raised — which is why IT is used in specialist settings such as some
medical, industrial process and safety-critical installations. It's uncommon in general UK
distribution.
At a Glance
| System | Installation earth | Typical max Ze | RCD for ADS? |
| TN-S | Supply earth (separate) | ≈ 0.8 Ω | Often not required |
| TN-C-S (PME) | Supply earth (PEN, split) | ≈ 0.35 Ω | Often not required |
| TT | Own electrode | ≈ 21 Ω (declared) | Yes |
| IT | Own electrode | — | Special (fault monitoring) |
Ze figures are the DNO's typical declared maxima — always use the value measured or declared for
the actual supply.
Why the System Governs Your Design
The earthing system sets the earth-fault loop impedance you start from, which decides whether an
overcurrent device disconnects in time or whether you need an RCD; it sets the main protective
bonding requirements (heaviest on PME); and it constrains specific applications such as EV
charging (Section 722) and swimming pools. It also feeds straight into cable sizing — the
fault level and the Zs
checks in a cable calculation depend on it. On HV
sites the earthing arrangement is a study in its own right; see
earth potential rise and our
earthing study design service.
Frequently Asked Questions
How do I know which earthing system I have?
Look at the supply intake: a TN-C-S (PME) supply has the main earth taken from the incoming neutral/PEN at the cut-out; a TN-S supply has a separate earth terminal, traditionally the lead sheath of the service cable; a TT supply has no earth from the DNO and relies on a local earth electrode. If in doubt, measure the external loop impedance (Ze) and ask the DNO — do not assume.
What is the difference between TN-S and TN-C-S?
In TN-S the neutral and protective earth are separate all the way from the source. In TN-C-S the supply combines them into one PEN conductor and they are only separated at the origin of the installation. TN-C-S usually has the lowest earth loop impedance but carries the open-PEN (broken combined conductor) risk.
What is the open-PEN (PME) risk?
On a TN-C-S (PME) supply the neutral and earth share one conductor up to the property. If that PEN conductor breaks in the network, the installation's earth can rise toward mains voltage, making earthed metalwork live. This is why PME systems require robust main protective bonding, and why outdoor EV charge points on PME need open-PEN protection or a TT arrangement.
Does a TT system need an RCD?
Almost always, yes. A TT earth electrode gives a high earth-fault loop impedance, so an overcurrent device usually cannot disconnect fast enough. BS 7671 requires an RCD for automatic disconnection, sized so that Ra × IΔn ≤ 50 V (the electrode resistance times the RCD rated residual current stays below the 50 V touch-voltage limit).
Can I install an EV charger on a PME (TN-C-S) supply?
Yes, but not by simply bonding to the PME earth outdoors. BS 7671 Section 722 requires either a charge point with built-in open-PEN detection, or a dedicated TT earth electrode for the charger, to remove the shock risk if the PEN conductor fails.
For the authoritative requirements, see BS 7671 Chapter 41 and the IET's
Wiring Matters
series.