Whether a circuit disconnects safely in a fault, what protective device you need, and how much bonding the job requires all depend on one thing decided before you draw a single cable: the earthing system. BS 7671 describes it with a short letter code — TN-S, TN-C-S, TN-C, TT, IT — and getting it right is the foundation of a safe design. Here is what each code means, how to tell which arrangement you have on site, and what changes in your calculations as a result.

The short version: the first letter says how the supply is earthed, the second how your installation is earthed. TN-C-S (PME) is the common modern UK supply — lowest loop impedance but an open-PEN risk; TN-S is a separate earth throughout; TT is your own electrode and needs an RCD; IT is a specialist, monitored arrangement; TN-C is not permitted for a consumer installation.

Try it: the earthing system explorer

Pick a system, then break something. The diagram redraws, the earth-fault loop is recalculated against the real BS 7671 limits, and the open-PEN scenario shows exactly how far the earthed metalwork can rise.

This interactive explorer needs JavaScript. Everything it demonstrates is also covered by the diagrams, tables and explanations below.

The naming code

The letters come from IEC 60364 and read left to right. Note that "earthing" and "grounding" are the same thing — the codes are international, so a TT grounding system and a TT earthing system are one and the same arrangement.

  • First letter — the supply's relationship to earth: T (terra) = one point, the transformer star point, is directly earthed; I = isolated from earth, or earthed only through a deliberate impedance.
  • Second letter — how your exposed metalwork is earthed: T = to your own local earth electrode; N = to the supply's earthed point, via a protective conductor supplied with the electricity.
  • Further letters (S / C) — how neutral and earth are arranged in the supply: S = separate conductors; C = combined into one conductor, the PEN.

What is a TN system?

TN is the umbrella. In any TN system of earthing, your exposed conductive parts are connected back to the supply's earthed point through a conductor that comes with the supply — not through an electrode of your own. That gives a metallic, low-impedance fault path, which is why TN systems can normally rely on an ordinary overcurrent device to disconnect an earth fault fast enough.

The letters that follow describe how neutral and earth are arranged inside that supply, and there are three arrangements: TN-S keeps them separate throughout, TN-C combines them throughout, and TN-C-S combines them in the distributor's network then separates them at the origin of your installation. Almost every modern UK supply is the last of those.

TN-S earthing system — separate earth throughout

TN-S earthing system schematic: a DNO transformer with an earthed star point supplies separate line, neutral and protective earth conductors all the way to the consumer unit and on to a Class I load, with no combined PEN conductor anywhere.TN-S earthing system schematic: a DNO transformer with an earthed star point supplies separate line, neutral and protective earth conductors all the way to the consumer unit and on to a Class I load, with no combined PEN conductor anywhere.
TN-S — neutral and protective earth are separate conductors from the transformer to the load. The earth is traditionally the sheath or armour of the service cable.

Neutral (N) and protective earth (PE) are separate conductors all the way from the transformer to the installation. The earth path is traditionally the metallic sheath or armour of the service cable. It gives a reliable, low-impedance earth and avoids the combined-conductor risk of PME entirely. Common on older urban supplies, and the typical declared maximum Ze is 0.8 Ω.

The one thing worth checking on an older TN-S service is that the earth really is still sound. Lead-sheathed cables corrode, and joints degrade; a supply that was TN-S when it was installed can behave very differently decades later. Measure Ze rather than trusting the label.

TN-C-S (PME) earthing system — combined, then separated

TN-C-S or PME earthing system schematic: a combined PEN conductor runs from the earthed transformer star point, earthed again at repeated network electrodes, and is split into separate neutral and protective earth at the origin of the installation before feeding the consumer unit and a Class I load.TN-C-S or PME earthing system schematic: a combined PEN conductor runs from the earthed transformer star point, earthed again at repeated network electrodes, and is split into separate neutral and protective earth at the origin of the installation before feeding the consumer unit and a Class I load.
TN-C-S (PME) — a combined PEN conductor supplies the property and is split into separate N and PE at the origin. Those repeated network electrodes are the "multiple" in Protective Multiple Earthing.

The supply brings a single PEN conductor — combined protective earth and neutral — to the property, and it is split into separate N and PE at the origin. This is Protective Multiple Earthing (PME), the standard modern UK arrangement. The "multiple" refers to the PEN being earthed repeatedly along the distributor's network, which is what keeps it close to earth potential in normal service.

It usually has the lowest external loop impedance — a typical declared maximum Ze of 0.35 Ω — so faults clear fast and cable sizing is easier. But it carries the open-PEN risk, and that single risk drives the strict main-bonding requirements on PME supplies and the special rules for outdoor EV charging.

The open-PEN fault

Open-PEN fault schematic on a PME supply: the combined PEN conductor is broken out in the distribution network, so load current diverts through the installation earthing and the exposed metalwork rises toward mains voltage.Open-PEN fault schematic on a PME supply: the combined PEN conductor is broken out in the distribution network, so load current diverts through the installation earthing and the exposed metalwork rises toward mains voltage.
The open-PEN fault — with the combined conductor broken out in the network, load current has no low-impedance route home and every earthed metal part can rise toward mains voltage.

If the combined conductor breaks out in the network, the installation's load current has no low-impedance route back to the transformer. It returns instead through whatever earth path the installation has — the main bonding, buried metal services, an electrode — and the whole earthed metalwork of the installation rises above true Earth by the voltage that current drops across that path. With a poor earth path, that voltage approaches the full supply voltage.

The maths behind the explorer's open-PEN mode is the condition in BS 7671 Annex A722.3, which underpins Regulation 722.411.4.1(b). It comes in two forms. For a single-phase installation the electrode resistance must satisfy Ra ≤ 70 × U0·Cmax / (Iinst × (U0·Cmax − 70)), where Cmax is 1.1. At a 60 A demand that is about 1.6 Ω; at 100 A it is under 1 Ω. A driven rod is typically tens of ohms, which is precisely why an electrode on its own almost never satisfies the requirement and why PEN-fault detection is the practical route.

For a three-phase installation the condition becomes Ra ≤ 70 × U0·Cmax / (Im × U0·Cmax − 70 × (IL1 + IL2 + IL3)), where Im is the neutral current from Annex A722.1: Im = √(IL1² + IL2² + IL3² − IL1IL2 − IL1IL3 − IL2IL3). Put Im = ΣIL = Iinst and it collapses back to the single-phase form, so they are one condition, not two.

The three-phase case carries a genuinely useful insight. A balanced three-phase load has almost no neutral current, so there is little to divert when the PEN breaks and the metalwork barely moves — at perfect balance, Im is zero and it does not move at all. That is why NOTE 1 lets you take 200 Ω whenever Im ≤ 70 × ΣIL / (U0·Cmax), and why the hazard is really a story about imbalance rather than about total demand. Switch the explorer's load to three-phase and drag the line currents together to watch it happen. Note also that these are all magnitudes, not phasors (NOTE 2).

TN-C earthing system — and why you will not see it

TN-C earthing system schematic: a single combined PEN conductor carries both neutral and protective earth from the transformer right through the consumer unit to the load, never splitting into separate conductors.TN-C earthing system schematic: a single combined PEN conductor carries both neutral and protective earth from the transformer right through the consumer unit to the load, never splitting into separate conductors.
TN-C — neutral and earth stay combined as one PEN conductor throughout, so there is no separate cpc and an RCD cannot work.

In a TN-C system the neutral and earth stay combined as a PEN conductor right through the installation — the split never happens. Two things follow. First, there is no separate protective conductor, so an RCD cannot work: an RCD detects the imbalance between line and neutral, and here the earth return is the neutral. Second, a break in the PEN anywhere makes every connected earthed part live.

BS 7671 does not permit TN-C for a general consumer installation. If you find a combined conductor continuing past the origin, that is a defect to be corrected — splitting it into separate N and PE at the origin is what turns it into TN-C-S. TN-C survives only in specific, controlled situations such as parts of a distributor's own network.

TT earthing system — your own earth electrode

TT earthing system schematic: the DNO supplies only line and neutral with no earth, and the installation makes its own connection to earth through a local electrode below the main earthing terminal, so earth-fault current returns through the mass of earth.TT earthing system schematic: the DNO supplies only line and neutral with no earth, and the installation makes its own connection to earth through a local electrode below the main earthing terminal, so earth-fault current returns through the mass of earth.
TT — no earth comes from the supply. The installation earths to its own electrode, so the fault loop runs through the mass of Earth and the impedance is high.

The distributor provides no earth; the installation makes its own connection to earth with a local electrode, usually one or more rods. Common in rural areas and wherever the supply is overhead. Because an electrode's resistance is high compared with a metallic supply earth, the earth-fault loop impedance is high — commonly a declared Ze of 21 Ω, and often much more in practice.

That is too high for an overcurrent device to clear an earth fault in time, so a TT system needs an RCD for automatic disconnection, sized so that Ra × IΔn ≤ 50 V (Regulation 411.5.3). For a 30 mA RCD that permits an electrode resistance up to 1,667 Ω, which is why a 30 mA device passes comfortably on almost any real electrode — but a 500 mA time-delayed device used upstream is limited to 100 Ω, and that one does bite.

IT earthing system — rare in the UK

IT earthing system schematic: the transformer star point is isolated or connected to earth only through a deliberate high impedance, while the installation earths its exposed metalwork to a local electrode, so a first earth fault produces no significant current.IT earthing system schematic: the transformer star point is isolated or connected to earth only through a deliberate high impedance, while the installation earths its exposed metalwork to a local electrode, so a first earth fault produces no significant current.
IT — the source is unearthed or earthed through a high impedance, so a first fault raises an alarm rather than tripping.

The supply is unearthed or earthed only through a high impedance, and exposed metalwork is earthed locally. A first fault does not cause a large fault current, so supply continuity is maintained and an insulation monitoring device raises an alarm instead of tripping. That is why IT is used where losing the supply is itself the hazard — some medical locations, industrial process plant and safety-critical installations. A second fault on a different line becomes a line-to-line fault and must be disconnected, so the protection is designed around that case. IT is uncommon in general UK distribution.

Which earthing system do I have?

Work from what you can see at the intake, then confirm it by measurement. The identifier below walks the same logic an engineer would use on site.

This interactive identifier needs JavaScript. In short: if the only earth is your own electrode it is TT (or IT if the source is not solidly earthed); if the supply earth is taken from the incoming neutral at the cut-out it is TN-C-S (PME); if it is a separate earth terminal or cable sheath it is TN-S. Confirm by measuring Ze and asking the DNO.

At a glance

System Installation earth Typical declared Ze Max disconnection time RCD for ADS? Main risk
TN-SSupply earth, separate PE≈ 0.8 Ω0.4 s final / 5 s distributionNot for ADSDeteriorated sheath earth
TN-C-S (PME)Supply earth via PEN, split at origin≈ 0.35 Ω0.4 s final / 5 s distributionNot for ADSOpen PEN
TN-CCombined PEN throughout≈ 0.35 Ω0.4 s final / 5 s distributionImpossibleNot permitted; broken PEN
TTOwn electrode≈ 21 Ω (often far more)0.2 s final / 1 s distributionYesHigh, variable Ra
ITOwn electrodeNot applicableFirst fault not disconnectedMonitoring, not ADSUndetected first fault

Ze figures are the DNO's typical declared maxima, not measured values — always use the figure measured or declared for the actual supply. "Not for ADS" means an RCD is not needed to achieve automatic disconnection; in practice RCDs are near-universal anyway because of Regulation 411.3.3 (socket-outlets up to 32 A) and 522.6.202 (cables concealed in walls).

Maximum Zs by protective device

On a TN system, the check is simply whether your measured Zs is below the maximum for the device. For circuit-breakers the figure is Zs = U0 × Cmin / Ia with U0 = 230 V and Cmin = 0.95, where Ia is 5 × In for a Type B, 10 × In for a Type C and 20 × In for a Type D. Fuses have no such formula and are read from the tables.

Rating Type B MCB Type C MCB Type D MCB BS 88-2 fuse
6 A7.28 Ω3.64 Ω1.82 Ω7.80 Ω
10 A4.37 Ω2.19 Ω1.09 Ω4.65 Ω
16 A2.73 Ω1.37 Ω0.68 Ω2.43 Ω
20 A2.19 Ω1.09 Ω0.55 Ω1.68 Ω
25 A1.75 Ω0.87 Ω0.44 Ω1.29 Ω
32 A1.37 Ω0.68 Ω0.34 Ω0.99 Ω
40 A1.09 Ω0.55 Ω0.27 Ω0.75 Ω
50 A0.87 Ω0.44 Ω0.22 Ω0.57 Ω
63 A0.69 Ω0.35 Ω0.17 Ω0.44 Ω

Maximum Zs for a 0.4 s disconnection time at U0 230 V — BS 7671 Table 41.3 for circuit-breakers and Table 41.2 for BS 88-2 fuses. Values apply at the conductor operating temperatures in the table notes; adjust a cold test reading accordingly. Indicative subset — verify against your own copy of BS 7671. On a TT system the limit is not from this table at all: it is 50 / IΔn.

Maximum disconnection times

SystemFinal circuit ≤ 63 ADistribution circuitReference
TN (all variants)0.4 s5 sTable 41.1, Reg 411.3.2.3
TT0.2 s1 sTable 41.1, Reg 411.3.2.4

AC systems with U0 between 120 V and 230 V. Note the exception under Table 41.1: where disconnection in a TT system is achieved by an overcurrent device and protective equipotential bonding is connected to all extraneous-conductive-parts per Regulation 411.3.1.2, the TN times (0.4 s / 5 s) may be used instead.

Main protective bonding on a PME supply

Bonding matters on every system, but on PME it is doing safety-critical work: it is what keeps everything in the building at the same potential when the PEN misbehaves. The minimum size is set by the copper-equivalent CSA of the supply PEN conductor, not by your main switch.

Copper-equivalent CSA of the PEN conductorMinimum main protective bonding conductor
35 mm² or less10 mm²
Over 35 up to 50 mm²16 mm²
Over 50 up to 95 mm²25 mm²
Over 95 up to 150 mm²35 mm²
Over 150 mm²50 mm²

BS 7671 Table 54.8. The distributor's local network conditions may require a larger conductor — ask. Where an installation has more than one PME source, size from the largest supply PEN.

Where PME must not be used

A PME earth is excellent right up until the PEN fails, and the situations where that failure would be lethal are precisely the ones BS 7671 carves out:

  • Outdoor EV charge points (Section 722). A PME earthing facility must not be used for a charge point outdoors, or one that could reasonably be used to charge a vehicle outdoors, unless Regulation 722.411.4.1(b)–(e) is met.
  • Caravans and motor caravans (Section 708), boats and marinas (Section 709). The person is in good contact with true earth and holding metalwork bonded to the PEN — the worst possible combination.
  • Petrol filling stations and similar hazardous areas. Potential differences between the PME earth and true earth in a zone containing flammable vapour are an ignition risk.
  • Swimming pools and other special locations where Part 7 imposes its own earthing and bonding requirements.

Converting PME to TT for an EV charge point

Where the electrode route is chosen, you are not converting the whole installation — you are creating a separate TT island for the charge point. In outline: the charge-point circuit gets its own earth electrode; that electrode's earth is kept separate from the PME main earthing terminal and far enough from any PME-earthed metalwork that the two earth zones do not interact; the circuit is protected by its own RCD; and the electrode resistance must satisfy the Annex A722.3 condition above, not merely the 50 V TT rule.

In practice this is hard to achieve and awkward to prove, which is why most installations use a charge point with built-in PEN-fault detection instead — a device meeting indent (c), which disconnects on a cpc-to-Earth rise above 70 V, or indent (d), which disconnects when the line-neutral voltage leaves the 207–253 V window. Read the manufacturer's declaration rather than assuming a unit has it.

Why the system governs your design

The earthing system is not a label you record at the end of the job — it is an input to almost every calculation you make:

  • It sets the Ze you start from, and therefore every Zs down the installation and whether your device disconnects in time or you need an RCD. Try it in the free BS 7671 cable sizing calculator, where the earthing system is one of the first board settings.
  • It sets the prospective fault current, which drives breaking capacity and the adiabatic check on your cpc — see the fault level guide.
  • It sets the main protective bonding requirements, heaviest on PME.
  • It constrains specific applications — EV charging, caravans, marinas, pools.
  • On HV sites the earthing arrangement is a study in its own right — see earth potential rise and our earthing study design service.

Glossary

PEN — a single conductor doing the job of both the protective earth and the neutral.

PE — protective earth: the conductor connecting exposed metalwork to the earthing terminal.

cpc — circuit protective conductor: the PE within a particular circuit.

MET — main earthing terminal: where the installation's earthing and bonding come together.

ADS — automatic disconnection of supply: the standard protective measure of Chapter 41.

Ze — the earth-fault loop impedance external to the installation, measured at the origin.

Zs — the total earth-fault loop impedance for a circuit: Ze plus that circuit's R1+R2.

Ra — the resistance of the earth electrode plus the protective conductor connecting it.

IΔn — an RCD's rated residual operating current, the level at which it must trip.

DNO — distribution network operator: the company that owns the network feeding the site.

Frequently Asked Questions

How do I know which earthing system I have?

Look at the supply intake. A TN-C-S (PME) supply takes the main earth from the incoming neutral/PEN at the cut-out, usually via a terminal block or link. A TN-S supply has a separate earth terminal, traditionally the lead sheath or armour of the service cable. A TT supply has no earth from the distributor at all and relies on a local earth electrode. If in doubt, measure the external loop impedance Ze and ask the DNO for the declared arrangement — do not assume.

What is a TN system?

TN is the umbrella term for any system where your exposed metalwork is earthed back to the supply's earthed point through a conductor supplied with the electricity, rather than through your own electrode. The letters after it say how neutral and earth are arranged in that supply: TN-S keeps them separate throughout, TN-C combines them into one PEN conductor throughout, and TN-C-S combines them in the supply then separates them at the origin of your installation.

What is the difference between TN-S and TN-C-S?

In TN-S the neutral and protective earth are separate conductors all the way from the source. In TN-C-S the supply combines them into one PEN conductor and they are separated only at the origin of the installation. TN-C-S usually has the lowest earth-fault loop impedance — a typical declared Ze of 0.35 Ω against 0.8 Ω for TN-S — but it carries the open-PEN risk that TN-S does not.

What is the open-PEN (PME) risk?

On a TN-C-S (PME) supply the neutral and earth share one conductor up to the property. If that PEN conductor breaks out in the distribution network, the load current has no low-impedance route back to the transformer and returns through the installation's earthing instead, so earthed metalwork can rise toward mains voltage. This is why PME systems require robust main protective bonding sized to Table 54.8, and why outdoor EV charge points on PME need open-PEN protection.

Does a TT system need an RCD?

Almost always, yes. A TT earth electrode gives a high earth-fault loop impedance, so an overcurrent device usually cannot disconnect fast enough. BS 7671 requires an RCD for automatic disconnection, sized so that Ra × IΔn ≤ 50 V — the electrode resistance times the RCD rated residual current must stay below the 50 V touch-voltage limit of Regulation 411.5.3.

What is the maximum Zs for a 32 A Type B MCB?

For a 32 A Type B circuit-breaker at U0 of 230 V, the maximum earth-fault loop impedance for 0.4 s disconnection is 1.37 Ω. It comes from Zs = U0 × Cmin / Ia, where Cmin is 0.95 and Ia for a Type B device is 5 × In, giving 0.95 × 230 / 160 = 1.37 Ω. The equivalent figures are 0.68 Ω for a Type C and 0.34 Ω for a Type D of the same rating.

What is TN-C and why is it not used in the UK?

TN-C keeps neutral and earth combined as a single PEN conductor right through the installation, so there is never a separate protective conductor. That makes an RCD impossible — an RCD works by detecting the imbalance between line and neutral, and in TN-C the earth return is the neutral. A broken PEN also makes every earthed part live. BS 7671 does not permit TN-C for a general consumer installation; the combined conductor must be split into separate N and PE at the origin, which makes it TN-C-S.

Can I install an EV charger on a PME (TN-C-S) supply?

Yes, but not by simply bonding to the PME earth outdoors. Regulation 722.411.4.1 requires one of: a dedicated installation earth electrode good enough to hold the main earthing terminal below 70 V during an open-PEN event; a device that disconnects on the cpc-to-Earth voltage exceeding 70 V; a device that disconnects when the line-neutral voltage leaves the 207–253 V window; or an equivalent means. Most real charge points use the voltage-window or PEN-fault-detection method built into the unit, because the electrode option is rarely achievable in practice.

Is an earthing system the same as a grounding system?

Yes — "earthing" is the UK and IEC term, "grounding" is the North American one, and the TN, TT and IT codes come from IEC 60364 so they mean the same thing either way. A TT grounding system and a TT earthing system are the same arrangement. The detailed rules differ between BS 7671 and the US NEC, so use the code that applies where the installation is.

Sources and verification. BS 7671:2018+A4:2026 Chapter 41 (Table 41.1 disconnection times, Tables 41.2–41.4 maximum Zs, Reg 411.5.3 for TT), Chapter 54 (Table 54.8 main protective bonding), Section 722 and Annex A722 (EV charging on PME). The figures on this page are an indicative subset for explanation — verify every value against your own copy of BS 7671 and the figures measured or declared for the actual supply. For wider background see the IET's Wiring Matters series.

Put It Into a Real Calculation

Our free BS 7671 cable sizing calculator runs the five checks — including the Zs check this page describes — and prints a calculation report. Or hand the whole design over to us.

Free Cable Sizing Calculator Earthing Study Design