Earthing Systems Explained: TN-S, TN-C-S (PME), TT & IT
Earthing · Updated 8 August 2026 · For contractors and project engineers
Whether a circuit disconnects safely in a fault, what protective device you need, and how much
bonding the job requires all depend on one thing decided before you draw a single cable: the
earthing system. BS 7671 describes it with a short letter code — TN-S, TN-C-S, TN-C, TT, IT —
and getting it right is the foundation of a safe design. Here is what each code means, how to
tell which arrangement you have on site, and what changes in your calculations as a result.
The short version: the first letter says how the supply is earthed,
the second how your installation is earthed. TN-C-S (PME) is the common modern UK
supply — lowest loop impedance but an open-PEN risk; TN-S is a separate earth throughout;
TT is your own electrode and needs an RCD; IT is a specialist, monitored arrangement; TN-C is
not permitted for a consumer installation.
Try it: the earthing system explorer
Pick a system, then break something. The diagram redraws, the earth-fault loop is recalculated
against the real BS 7671 limits, and the open-PEN scenario shows exactly how far the earthed
metalwork can rise.
This interactive explorer needs JavaScript. Everything it demonstrates is also covered by the
diagrams, tables and explanations below.
The naming code
The letters come from IEC 60364 and read left to right. Note that "earthing" and "grounding"
are the same thing — the codes are international, so a TT grounding system and a TT earthing
system are one and the same arrangement.
First letter — the supply's relationship to earth:T (terra) = one point, the transformer star point, is directly earthed; I = isolated from earth, or earthed only through a deliberate impedance.
Second letter — how your exposed metalwork is earthed:T = to your own local earth electrode; N = to the supply's earthed point, via a protective conductor supplied with the electricity.
Further letters (S / C) — how neutral and earth are arranged in the supply:S = separate conductors; C = combined into one conductor, the PEN.
What is a TN system?
TN is the umbrella. In any TN system of earthing, your exposed conductive parts
are connected back to the supply's earthed point through a conductor that comes with the
supply — not through an electrode of your own. That gives a metallic, low-impedance fault path,
which is why TN systems can normally rely on an ordinary overcurrent device to disconnect an
earth fault fast enough.
The letters that follow describe how neutral and earth are arranged inside that supply, and
there are three arrangements: TN-S keeps them separate throughout,
TN-C combines them throughout, and TN-C-S combines them in the
distributor's network then separates them at the origin of your installation. Almost every
modern UK supply is the last of those.
TN-S earthing system — separate earth throughout
TN-S — neutral and protective earth are separate conductors from the transformer to the load. The earth is traditionally the sheath or armour of the service cable.
Neutral (N) and protective earth (PE) are separate conductors all the way from the transformer
to the installation. The earth path is traditionally the metallic sheath or armour of the
service cable. It gives a reliable, low-impedance earth and avoids the combined-conductor risk
of PME entirely. Common on older urban supplies, and the typical declared maximum Ze is
0.8 Ω.
The one thing worth checking on an older TN-S service is that the earth really is still sound.
Lead-sheathed cables corrode, and joints degrade; a supply that was TN-S when it was installed
can behave very differently decades later. Measure Ze rather than trusting the label.
TN-C-S (PME) earthing system — combined, then separated
TN-C-S (PME) — a combined PEN conductor supplies the property and is split into separate N and PE at the origin. Those repeated network electrodes are the "multiple" in Protective Multiple Earthing.
The supply brings a single PEN conductor — combined protective earth and
neutral — to the property, and it is split into separate N and PE at the origin. This is
Protective Multiple Earthing (PME), the standard modern UK arrangement. The
"multiple" refers to the PEN being earthed repeatedly along the distributor's network, which is
what keeps it close to earth potential in normal service.
It usually has the lowest external loop impedance — a typical declared maximum Ze of
0.35 Ω — so faults clear fast and cable sizing is easier. But it carries
the open-PEN risk, and that single risk drives the strict main-bonding
requirements on PME supplies and the special rules for outdoor EV charging.
The open-PEN fault
The open-PEN fault — with the combined conductor broken out in the network, load current has no low-impedance route home and every earthed metal part can rise toward mains voltage.
If the combined conductor breaks out in the network, the installation's load current has no
low-impedance route back to the transformer. It returns instead through whatever earth path the
installation has — the main bonding, buried metal services, an electrode — and the whole
earthed metalwork of the installation rises above true Earth by the voltage that current drops
across that path. With a poor earth path, that voltage approaches the full supply voltage.
The maths behind the explorer's open-PEN mode is the condition in BS 7671 Annex A722.3, which
underpins Regulation 722.411.4.1(b). It comes in two forms. For a
single-phase installation the electrode resistance must satisfy
Ra ≤ 70 × U0·Cmax / (Iinst × (U0·Cmax − 70)), where Cmax is 1.1. At a 60 A
demand that is about 1.6 Ω; at 100 A it is under
1 Ω. A driven rod is typically tens of ohms, which is precisely why an
electrode on its own almost never satisfies the requirement and why PEN-fault detection is the
practical route.
For a three-phase installation the condition becomes
Ra ≤ 70 × U0·Cmax / (Im × U0·Cmax − 70 × (IL1 + IL2 + IL3)),
where Im is the neutral current from Annex A722.1:
Im = √(IL1² + IL2² + IL3² − IL1IL2
− IL1IL3 − IL2IL3). Put
Im = ΣIL = Iinst and it collapses back to the single-phase form, so they are one
condition, not two.
The three-phase case carries a genuinely useful insight. A balanced three-phase load
has almost no neutral current, so there is little to divert when the PEN breaks and the
metalwork barely moves — at perfect balance, Im is zero and it does not move at all. That is
why NOTE 1 lets you take 200 Ω whenever
Im ≤ 70 × ΣIL / (U0·Cmax), and why the hazard is really a story about
imbalance rather than about total demand. Switch the explorer's load to three-phase
and drag the line currents together to watch it happen. Note also that these are all
magnitudes, not phasors (NOTE 2).
TN-C earthing system — and why you will not see it
TN-C — neutral and earth stay combined as one PEN conductor throughout, so there is no separate cpc and an RCD cannot work.
In a TN-C system the neutral and earth stay combined as a PEN conductor right through the
installation — the split never happens. Two things follow. First, there is no separate
protective conductor, so an RCD cannot work: an RCD detects the imbalance
between line and neutral, and here the earth return is the neutral. Second, a break in
the PEN anywhere makes every connected earthed part live.
BS 7671 does not permit TN-C for a general consumer installation. If you find a combined
conductor continuing past the origin, that is a defect to be corrected — splitting it into
separate N and PE at the origin is what turns it into TN-C-S. TN-C survives only in specific,
controlled situations such as parts of a distributor's own network.
TT earthing system — your own earth electrode
TT — no earth comes from the supply. The installation earths to its own electrode, so the fault loop runs through the mass of Earth and the impedance is high.
The distributor provides no earth; the installation makes its own connection to earth with a
local electrode, usually one or more rods. Common in rural areas and wherever the supply is
overhead. Because an electrode's resistance is high compared with a metallic supply earth, the
earth-fault loop impedance is high — commonly a declared Ze of 21 Ω, and
often much more in practice.
That is too high for an overcurrent device to clear an earth fault in time, so a
TT system needs an RCD for automatic disconnection, sized so that
Ra × IΔn ≤ 50 V (Regulation 411.5.3). For a 30 mA RCD that permits an
electrode resistance up to 1,667 Ω, which is why a 30 mA device passes comfortably on
almost any real electrode — but a 500 mA time-delayed device used upstream is limited to
100 Ω, and that one does bite.
IT earthing system — rare in the UK
IT — the source is unearthed or earthed through a high impedance, so a first fault raises an alarm rather than tripping.
The supply is unearthed or earthed only through a high impedance, and exposed metalwork is
earthed locally. A first fault does not cause a large fault current, so supply continuity is
maintained and an insulation monitoring device raises an alarm instead of tripping. That is why
IT is used where losing the supply is itself the hazard — some medical locations, industrial
process plant and safety-critical installations. A second fault on a different line
becomes a line-to-line fault and must be disconnected, so the protection is designed around
that case. IT is uncommon in general UK distribution.
Which earthing system do I have?
Work from what you can see at the intake, then confirm it by measurement. The identifier below
walks the same logic an engineer would use on site.
This interactive identifier needs JavaScript. In short: if the only earth is your own
electrode it is TT (or IT if the source is not solidly earthed); if the supply earth is taken
from the incoming neutral at the cut-out it is TN-C-S (PME); if it is a separate earth
terminal or cable sheath it is TN-S. Confirm by measuring Ze and asking the DNO.
At a glance
System
Installation earth
Typical declared Ze
Max disconnection time
RCD for ADS?
Main risk
TN-S
Supply earth, separate PE
≈ 0.8 Ω
0.4 s final / 5 s distribution
Not for ADS
Deteriorated sheath earth
TN-C-S (PME)
Supply earth via PEN, split at origin
≈ 0.35 Ω
0.4 s final / 5 s distribution
Not for ADS
Open PEN
TN-C
Combined PEN throughout
≈ 0.35 Ω
0.4 s final / 5 s distribution
Impossible
Not permitted; broken PEN
TT
Own electrode
≈ 21 Ω (often far more)
0.2 s final / 1 s distribution
Yes
High, variable Ra
IT
Own electrode
Not applicable
First fault not disconnected
Monitoring, not ADS
Undetected first fault
Ze figures are the DNO's typical declared maxima, not measured values — always use the figure
measured or declared for the actual supply. "Not for ADS" means an RCD is not needed to achieve
automatic disconnection; in practice RCDs are near-universal anyway because of Regulation
411.3.3 (socket-outlets up to 32 A) and 522.6.202 (cables concealed in walls).
Maximum Zs by protective device
On a TN system, the check is simply whether your measured Zs is below the maximum for the
device. For circuit-breakers the figure is Zs = U0 × Cmin / Ia with U0 = 230 V
and Cmin = 0.95, where Ia is 5 × In for a Type B, 10 × In for a Type C and 20 × In
for a Type D. Fuses have no such formula and are read from the tables.
Rating
Type B MCB
Type C MCB
Type D MCB
BS 88-2 fuse
6 A
7.28 Ω
3.64 Ω
1.82 Ω
7.80 Ω
10 A
4.37 Ω
2.19 Ω
1.09 Ω
4.65 Ω
16 A
2.73 Ω
1.37 Ω
0.68 Ω
2.43 Ω
20 A
2.19 Ω
1.09 Ω
0.55 Ω
1.68 Ω
25 A
1.75 Ω
0.87 Ω
0.44 Ω
1.29 Ω
32 A
1.37 Ω
0.68 Ω
0.34 Ω
0.99 Ω
40 A
1.09 Ω
0.55 Ω
0.27 Ω
0.75 Ω
50 A
0.87 Ω
0.44 Ω
0.22 Ω
0.57 Ω
63 A
0.69 Ω
0.35 Ω
0.17 Ω
0.44 Ω
Maximum Zs for a 0.4 s disconnection time at U0 230 V — BS 7671 Table 41.3 for
circuit-breakers and Table 41.2 for BS 88-2 fuses. Values apply at the conductor operating
temperatures in the table notes; adjust a cold test reading accordingly. Indicative subset —
verify against your own copy of BS 7671. On a TT system the limit is not from
this table at all: it is 50 / IΔn.
Maximum disconnection times
System
Final circuit ≤ 63 A
Distribution circuit
Reference
TN (all variants)
0.4 s
5 s
Table 41.1, Reg 411.3.2.3
TT
0.2 s
1 s
Table 41.1, Reg 411.3.2.4
AC systems with U0 between 120 V and 230 V. Note the exception under Table 41.1: where
disconnection in a TT system is achieved by an overcurrent device and protective
equipotential bonding is connected to all extraneous-conductive-parts per Regulation 411.3.1.2,
the TN times (0.4 s / 5 s) may be used instead.
Main protective bonding on a PME supply
Bonding matters on every system, but on PME it is doing safety-critical work: it is what keeps
everything in the building at the same potential when the PEN misbehaves. The minimum size is
set by the copper-equivalent CSA of the supply PEN conductor, not by your main switch.
Copper-equivalent CSA of the PEN conductor
Minimum main protective bonding conductor
35 mm² or less
10 mm²
Over 35 up to 50 mm²
16 mm²
Over 50 up to 95 mm²
25 mm²
Over 95 up to 150 mm²
35 mm²
Over 150 mm²
50 mm²
BS 7671 Table 54.8. The distributor's local network conditions may require a larger conductor —
ask. Where an installation has more than one PME source, size from the largest supply PEN.
Where PME must not be used
A PME earth is excellent right up until the PEN fails, and the situations where that failure
would be lethal are precisely the ones BS 7671 carves out:
Outdoor EV charge points (Section 722). A PME earthing facility must not be used for a charge point outdoors, or one that could reasonably be used to charge a vehicle outdoors, unless Regulation 722.411.4.1(b)–(e) is met.
Caravans and motor caravans (Section 708), boats and marinas (Section 709). The person is in good contact with true earth and holding metalwork bonded to the PEN — the worst possible combination.
Petrol filling stations and similar hazardous areas. Potential differences between the PME earth and true earth in a zone containing flammable vapour are an ignition risk.
Swimming pools and other special locations where Part 7 imposes its own earthing and bonding requirements.
Converting PME to TT for an EV charge point
Where the electrode route is chosen, you are not converting the whole installation — you are
creating a separate TT island for the charge point. In outline: the charge-point circuit gets
its own earth electrode; that electrode's earth is kept separate from the PME main
earthing terminal and far enough from any PME-earthed metalwork that the two earth zones do not
interact; the circuit is protected by its own RCD; and the electrode resistance must satisfy
the Annex A722.3 condition above, not merely the 50 V TT rule.
In practice this is hard to achieve and awkward to prove, which is why most installations use a
charge point with built-in PEN-fault detection instead — a device meeting indent (c), which
disconnects on a cpc-to-Earth rise above 70 V, or indent (d), which disconnects when the
line-neutral voltage leaves the 207–253 V window. Read the manufacturer's declaration
rather than assuming a unit has it.
Why the system governs your design
The earthing system is not a label you record at the end of the job — it is an input to almost
every calculation you make:
It sets the Ze you start from, and therefore every Zs down the installation and whether your device disconnects in time or you need an RCD. Try it in the free BS 7671 cable sizing calculator, where the earthing system is one of the first board settings.
It sets the prospective fault current, which drives breaking capacity and the adiabatic check on your cpc — see the fault level guide.
It sets the main protective bonding requirements, heaviest on PME.
It constrains specific applications — EV charging, caravans, marinas, pools.
PEN — a single conductor doing the job of both the protective earth and the neutral.
PE — protective earth: the conductor connecting exposed metalwork to the earthing terminal.
cpc — circuit protective conductor: the PE within a particular circuit.
MET — main earthing terminal: where the installation's earthing and bonding come together.
ADS — automatic disconnection of supply: the standard protective measure of Chapter 41.
Ze — the earth-fault loop impedance external to the installation, measured at the origin.
Zs — the total earth-fault loop impedance for a circuit: Ze plus that circuit's R1+R2.
Ra — the resistance of the earth electrode plus the protective conductor connecting it.
IΔn — an RCD's rated residual operating current, the level at which it must trip.
DNO — distribution network operator: the company that owns the network feeding the site.
Frequently Asked Questions
How do I know which earthing system I have?
Look at the supply intake. A TN-C-S (PME) supply takes the main earth from the incoming neutral/PEN at the cut-out, usually via a terminal block or link. A TN-S supply has a separate earth terminal, traditionally the lead sheath or armour of the service cable. A TT supply has no earth from the distributor at all and relies on a local earth electrode. If in doubt, measure the external loop impedance Ze and ask the DNO for the declared arrangement — do not assume.
What is a TN system?
TN is the umbrella term for any system where your exposed metalwork is earthed back to the supply's earthed point through a conductor supplied with the electricity, rather than through your own electrode. The letters after it say how neutral and earth are arranged in that supply: TN-S keeps them separate throughout, TN-C combines them into one PEN conductor throughout, and TN-C-S combines them in the supply then separates them at the origin of your installation.
What is the difference between TN-S and TN-C-S?
In TN-S the neutral and protective earth are separate conductors all the way from the source. In TN-C-S the supply combines them into one PEN conductor and they are separated only at the origin of the installation. TN-C-S usually has the lowest earth-fault loop impedance — a typical declared Ze of 0.35 Ω against 0.8 Ω for TN-S — but it carries the open-PEN risk that TN-S does not.
What is the open-PEN (PME) risk?
On a TN-C-S (PME) supply the neutral and earth share one conductor up to the property. If that PEN conductor breaks out in the distribution network, the load current has no low-impedance route back to the transformer and returns through the installation's earthing instead, so earthed metalwork can rise toward mains voltage. This is why PME systems require robust main protective bonding sized to Table 54.8, and why outdoor EV charge points on PME need open-PEN protection.
Does a TT system need an RCD?
Almost always, yes. A TT earth electrode gives a high earth-fault loop impedance, so an overcurrent device usually cannot disconnect fast enough. BS 7671 requires an RCD for automatic disconnection, sized so that Ra × IΔn ≤ 50 V — the electrode resistance times the RCD rated residual current must stay below the 50 V touch-voltage limit of Regulation 411.5.3.
What is the maximum Zs for a 32 A Type B MCB?
For a 32 A Type B circuit-breaker at U0 of 230 V, the maximum earth-fault loop impedance for 0.4 s disconnection is 1.37 Ω. It comes from Zs = U0 × Cmin / Ia, where Cmin is 0.95 and Ia for a Type B device is 5 × In, giving 0.95 × 230 / 160 = 1.37 Ω. The equivalent figures are 0.68 Ω for a Type C and 0.34 Ω for a Type D of the same rating.
What is TN-C and why is it not used in the UK?
TN-C keeps neutral and earth combined as a single PEN conductor right through the installation, so there is never a separate protective conductor. That makes an RCD impossible — an RCD works by detecting the imbalance between line and neutral, and in TN-C the earth return is the neutral. A broken PEN also makes every earthed part live. BS 7671 does not permit TN-C for a general consumer installation; the combined conductor must be split into separate N and PE at the origin, which makes it TN-C-S.
Can I install an EV charger on a PME (TN-C-S) supply?
Yes, but not by simply bonding to the PME earth outdoors. Regulation 722.411.4.1 requires one of: a dedicated installation earth electrode good enough to hold the main earthing terminal below 70 V during an open-PEN event; a device that disconnects on the cpc-to-Earth voltage exceeding 70 V; a device that disconnects when the line-neutral voltage leaves the 207–253 V window; or an equivalent means. Most real charge points use the voltage-window or PEN-fault-detection method built into the unit, because the electrode option is rarely achievable in practice.
Is an earthing system the same as a grounding system?
Yes — "earthing" is the UK and IEC term, "grounding" is the North American one, and the TN, TT and IT codes come from IEC 60364 so they mean the same thing either way. A TT grounding system and a TT earthing system are the same arrangement. The detailed rules differ between BS 7671 and the US NEC, so use the code that applies where the installation is.
Sources and verification. BS 7671:2018+A4:2026 Chapter 41 (Table 41.1
disconnection times, Tables 41.2–41.4 maximum Zs, Reg 411.5.3 for TT), Chapter 54
(Table 54.8 main protective bonding), Section 722 and Annex A722 (EV charging on PME).
The figures on this page are an indicative subset for explanation — verify every value against
your own copy of BS 7671 and the figures measured or declared for the actual supply. For wider
background see the IET's
Wiring Matters series.
Put It Into a Real Calculation
Our free BS 7671 cable sizing calculator runs the five checks — including the Zs check this page describes — and prints a calculation report. Or hand the whole design over to us.