"How many lux?" sounds like it should have a one-word answer, but a compliant lighting design is never a single number. BS EN 12464-1 sets a maintained illuminance for each task — and a glare limit, a uniformity and a colour-rendering requirement to go with it. Here are the numbers people ask for, and the three things a lux figure alone leaves out.

The short version: the standard gives a maintained lux level per task (office 500, corridor 100, warehouse storage 150…), plus a glare limit (UGR), a uniformity (Uo) and a colour-rendering minimum (Ra). You design above the lux target so it's still met at the end of the maintenance cycle.

Typical Maintained Levels

Area / taskMaintained lux (Em)UGR limit
General office (writing, typing, reading)500≤ 19
Reception / filing300≤ 22
Meeting / conference room500≤ 19
Corridors / circulation100≤ 25 (28)
Stairs100–150≤ 25
Warehouse storage (stacking)150
Order picking / continuous work300≤ 22
Loading bay150≤ 25

Indicative values for common tasks — the standard lists many more, and the current edition adds context (task, immediate surround and background areas) with modifier ranges. Always design to the specific task and the current BS EN 12464-1.

A Lux Number Isn't Enough — the Other Three

  • Uniformity (Uo). The ratio of minimum to average illuminance on the task area — commonly ≥ 0.6 — so you don't get bright pools and dim gaps.
  • Glare (UGR). The Unified Glare Rating limits discomfort from the fittings themselves (≤ 19 in offices). A layout can hit the lux target and still fail on glare.
  • Colour rendering (Ra). How faithfully colours appear under the light — typically Ra ≥ 80 for interiors where people work.

The current standard also sets minimum levels on the walls and ceiling and considers cylindrical illuminance for faces and visual communication — lighting the room, not just the desk.

Why You Design Above the Target: The Maintenance Factor

"Maintained" is the key word. Lamp output falls with age and fittings collect dust, so the illuminance on day one has to be higher than the target for it to still be met at the end of the maintenance cycle. That headroom is the maintenance factor (MF) — design to Em / MF initially. A design quoted at exactly the target with no maintenance factor is already non-compliant the moment the lamps depreciate.

What This Means for Your Design

Meeting all four criteria — lux, uniformity, glare and colour rendering, with a realistic maintenance factor — is a calculation on the actual room, luminaire and layout, not a spacing rule. Our DIALux lighting design service produces illuminance and UGR calculations to BS EN 12464-1 with the maintenance factor stated, and covers emergency lighting to BS 5266 alongside the normal scheme.

Frequently Asked Questions

How many lux do you need for an office?

BS EN 12464-1 sets 500 lux maintained for general office work — writing, typing, reading and data processing — with a glare limit of UGR ≤ 19, uniformity Uo ≥ 0.6 and colour rendering Ra ≥ 80. Reception desks and filing areas are typically 300 lux, and archives around 200 lux.

What lux level does a warehouse need?

Around 150 lux maintained for storage and stacking areas that are not continuously occupied, rising to about 300 lux for order-picking and areas where people work continuously. Loading bays are typically 150 lux. Continuously occupied spaces have a minimum of 200 lux under the current standard.

What is maintained illuminance?

The illuminance (Em) that must be maintained on the task area over the whole maintenance cycle — not the day the lamps are new. Because output falls as lamps age and fittings collect dirt, you design to a higher initial level and apply a maintenance factor so it never drops below the target before the next clean or re-lamp.

What is UGR?

Unified Glare Rating — a measure of discomfort glare from the luminaires in a space. BS EN 12464-1 sets a limit for each task (for example UGR ≤ 19 in offices, ≤ 22 in many industrial areas). A compliant lighting design has to meet the glare limit as well as the lux level.

What lux level is needed for corridors and stairs?

Circulation areas and corridors are typically 100 lux maintained, and stairs around 100–150 lux with attention to modelling so the steps read clearly. These are lower than task areas but still have uniformity and glare requirements.