A cable that's big enough to carry the current can still be too small — because by the time the
supply reaches the far end of a long run, the voltage has sagged below what the equipment needs.
BS 7671 puts a limit on that sag. Here's how the 3% and 5% rules work, how to calculate voltage
drop, and what to do when a circuit fails it.
The short version: keep the drop from the origin to the load within 3% for
lighting and 5% for everything else (public supply). Work it out with
VD = mV/A/m × Ib × L / 1000, and remember it's cumulative —
submain plus final circuit.
The Limits (Regulation 525)
For an installation supplied directly from the public LV network, the permitted voltage drop from
the origin to any point of use is:
| Circuit | Limit | 230 V | 400 V |
| Lighting | 3% | 6.9 V | 12 V |
| Other uses (power) | 5% | 11.5 V | 20 V |
Fed from a private source (own transformer or generator) instead of the public network, the
limits rise to 6% and 8%.
The Formula
Every cable size has a tabulated voltage-drop figure in millivolts per ampere per metre
(mV/A/m) in BS 7671 Appendix 4. The drop is:
Vd = (mV/A/m × Ib × L) / 1000
with Ib the design current and L the length in metres. For sizes of 25 mm²
and above the tables split the value into resistive (r) and reactive (x) parts because
inductance starts to matter, and you combine them with the load's power factor; below that,
the single (z) figure is fine.
Worked example: a 32 A circuit on 4 mm² twin-and-earth
(11 mV/A/m) over 25 m drops
11 × 32 × 25 / 1000 = 8.8 V, which is
3.8% of 230 V. Fine as a power circuit (under 5%), but it would fail the 3% lighting limit —
you'd move to 6 mm² or shorten the run.
It's Cumulative — Origin to Load
The limit applies to the whole path, not each circuit in isolation. A final circuit fed through a
long submain shares the submain's drop, so a final circuit that passes on its own can fail once
the submain is added. On a real network this bookkeeping is where hand calculations go wrong —
the drop at a socket depends on every cable upstream of it, and a change to the submain silently
changes every circuit it feeds.
If a Circuit Fails
- Increase the conductor size — the most direct fix; halving the mV/A/m roughly halves the drop.
- Shorten the route or move the distribution board closer to the load centre.
- Split the load across more circuits so each carries less current.
- Check the assumption — is the full design current really continuous, and is the route length as long as assumed?
Where This Fits
Voltage drop is one of the five checks in a compliant
cable calculation, alongside
current-carrying capacity (with derating
factors), earth-fault loop impedance and the adiabatic check. Because it's cumulative and
network-wide, it's exactly the sort of thing calculation software gets right and spreadsheets
get wrong when a design changes.
Frequently Asked Questions
What is the maximum voltage drop allowed by BS 7671?
For an installation supplied from the public low-voltage network, BS 7671 Regulation 525 limits voltage drop to 3% for lighting and 5% for other uses, measured from the origin of the installation to the load. At 230 V single-phase that is 6.9 V and 11.5 V; at 400 V three-phase, 12 V and 20 V.
How do you calculate voltage drop?
Voltage drop = (mV/A/m × Ib × L) / 1000, where mV/A/m is the cable's tabulated value from BS 7671 Appendix 4, Ib is the design current in amps, and L is the length in metres. Divide the result by the nominal voltage to get the percentage.
Is voltage drop measured per circuit or from the origin?
From the origin of the installation to the point of use — so it is cumulative. The drop across a submain and the final circuit it feeds must be added together and the total kept within the limit. That is why a final circuit that passes on its own can still fail once the submain drop is included.
What do I do if the voltage drop is too high?
Increase the conductor size, shorten the cable route, move the distribution board nearer the load, or split the load across more circuits. On a network it is often cheaper to uprate one submain than several final circuits.
Do the limits change for a private supply?
Yes. Where the installation is fed from a private source such as its own transformer or a generator rather than the public network, BS 7671 allows higher limits — 6% for lighting and 8% for other uses — because the supply voltage is under the installation owner's control.