MEP Bracket Calculator
Calculation basis and reference data
Every number this calculator uses, where it came from, and how each check is worked out. Written to be reproduced: if you cannot follow a figure on an issued sheet back to a catalogue page or a clause here, that is a fault in this document.
How a bracket is calculated
Weight starts on the containment and ends in the structure. Every check asks the same question at a different point on that path: can this part carry what is passing through it?
Lh it becomes a weight sitting on one bracket, at the position it
actually occupies. That weight bends the channel, divides between the rods according to where it
sits, and arrives at the structure through the fixings. Each check below sits at one point on
this path.There are six checks on a plain bracket, plus two more that appear only when they apply. They are all the same shape: a demand computed from the load, against a capacity read from a catalogue or a standard, reported as a percentage. Nothing passes on a missing capacity — a value the tool does not hold reads NO DATA, never a silent pass.
Channel capacity
The bearer's strength and stiffness, straight off the manufacturer's load table. One row per span, three ambient columns and — on the fire-rated sections — three more.
The Fmax column is a strength value: the total uniformly distributed
load the section carries on a simply supported span at an allowable bending stress of
σ = 175 N/mm². The L/200 and L/360 columns are
deflection values — the load at which the span sags to that fraction of its length.
Where the catalogue prints a dash, deflection does not govern at that span, or the section is off
the end of its published deflection table.
| ambient | |||
|---|---|---|---|
| Span m | Fmax kN | L/200 kN | L/360 kN |
| 0.25 | 16.069 | — | — |
| 0.50 | 8.034 | — | — |
| 0.75 | 5.356 | — | 4.738 |
| 1.00 | 4.012 | — | 2.659 |
| 1.25 | 3.208 | 3.071 | 1.707 |
| 1.50 | 2.678 | 2.129 | 1.177 |
| 1.75 | 2.296 | 1.56 | 0.863 |
| 2.00 | 2.001 | 1.197 | 0.657 |
| 2.25 | 1.785 | 0.942 | 0.52 |
| 2.50 | 1.599 | 0.765 | 0.422 |
| 2.75 | 1.452 | 0.628 | 0.343 |
| 3.00 | 1.334 | 0.53 | 0.294 |
| fire-tested | |||
|---|---|---|---|
| Span m | 30 min kN | 1 h kN | 2 h kN |
| 0.50 | 6.0255 | 3.37428 | 1.607 |
| 0.75 | 4.017 | 2.24952 | 1.071 |
| 1.00 | 3.009 | 1.68504 | 0.802 |
| 1.25 | 2.406 | 1.34736 | 0.642 |
| 1.50 | 2.0085 | 1.12476 | 0.536 |
| 1.75 | 1.722 | 0.96432 | 0.459 |
| over 1.75 | not published — the edge of the test, see section 8 | ||
| ambient | |||
|---|---|---|---|
| Span m | Fmax kN | L/200 kN | L/360 kN |
| 0.75 | 16.363 | — | — |
| 1.00 | 12.272 | — | — |
| 1.25 | 9.82 | — | — |
| 1.50 | 8.182 | — | 7.034 |
| 1.75 | 7.014 | — | 5.17 |
| 2.00 | 6.131 | — | 3.953 |
| 2.25 | 5.454 | — | 3.12 |
| 2.50 | 4.905 | 4.552 | 2.531 |
| 2.75 | 4.464 | 3.767 | 2.09 |
| 3.00 | 4.091 | 3.159 | 1.756 |
| fire-tested | |||
|---|---|---|---|
| Span m | 30 min kN | 1 h kN | 2 h kN |
| 0.75 | 12.2723 | 6.8276 | 3.2726 |
| 1.00 | 9.204 | 5.15242 | 2.4544 |
| 1.25 | 7.365 | 4.1244 | 1.964 |
| 1.50 | 6.1365 | 3.43644 | 1.6364 |
| 1.75 | 5.2605 | 2.94588 | 1.4028 |
| 2.00 | 4.59825 | 2.57502 | 1.2262 |
| over 2.00 | not published — the edge of the test, see section 8 | ||
One error worth knowing. The Material Approval Request prints the
ambient load at 1.50 m as 2.0678 kN. The catalogue gives 2.678. The
sequence 3.208 → 2.0678 → 2.296 is not monotonic, which a load/span curve cannot be,
and the fire values at that span are 0.75 / 0.42 / 0.20 of 2.678. It is a digit
transposition in the submittal; this tool holds the catalogue value.
A plain structural channel
Two hot-rolled channels are offered beside the Unistrut sections, each usable either way up. Their tables are the only ones in this document that nobody published — they are calculated, so the calculation is set out here in full.
Unistrut print load/span tables because the channel is their product. A 76 × 38
tapered flange channel or a 100 × 50 parallel flange channel is a
structural section: no manufacturer publishes a bracket load table for one, and none will. You
calculate it. That is not a weaker footing than a transcription — it is the same identity
section 7 shows holding to 0.02 % down Unistrut's own printed column, run on a different
Z.
| web vertical | laid flat | ||||||
|---|---|---|---|---|---|---|---|
| Section | kg/m | A cm2 | Ixx cm4 | Zxx cm3 | Iyy cm4 | Zyy cm3 | Source |
| 76×38×6.71 TFC (BS 4-1) | 6.710 | 8.56 | 74.3 | 19.5 | 10.7 | 4.09 | BS 4-1 not in P363 |
| 100×50×10 PFC (SCI P363) | 10.200 | 13.00 | 208 | 41.5 | 32.3 | 9.9 | SCI P363 Blue Book |
The three formulae
σ = 165 N/mm² is 0.6 × the 275 N/mm² yield of S275. With the
tool's default load factor of 1.3 that is 2.17 overall against yield, which sits alongside the 2.08
implied by Unistrut's own σ = 175. It is a choice, not a published value, and it
is the one figure on this page most worth agreeing before you rely on a result.
Fire needs no test. BS 8519:2020 Annex E is normative, and it says the stresses in Table E.1 apply to unprotected drop rods and bearers made of mild steel. A plain steel bearer is a bearer. So the fire columns are the same formula at 9 / 9 / 6 N/mm² — the standard applied directly, rather than read across from a furnace test of a different arrangement the way section 8 has to do for the FR strut.
| Catalogue section | Limit | Values | I back-solved cm4 | Range | Spread |
|---|---|---|---|---|---|
| P1000T | L/200 | 8 | 5.925 | 5.889 - 5.950 | 1.04% |
| P1000T | L/360 | 10 | 5.897 | 5.790 - 5.954 | 2.82% |
| P1001TFR | L/200 | 3 | 35.288 | 35.257 - 35.327 | 0.20% |
| P1001TFR | L/360 | 7 | 35.298 | 35.257 - 35.342 | 0.24% |
| P3300T10 | L/200 | 5 | 1.015 | 1.014 - 1.016 | 0.16% |
| P3300T10 | L/360 | 4 | 1.015 | 1.015 - 1.016 | 0.08% |
W = 384EI/(5rL²) is the relationship behind a published
deflection column, then I comes back the same off every span in it. It does —
to a fifth of a percent on the two sections printed to four significant figures. The P1000T's
columns are printed to 3 dp and one row (2.75 m, L/360) sits about 2 % off the rest, which is
what widens its spread. Note the back-solved I is a few percent under the gross
I published for that section: it is continuously slotted. A plain channel has no
slots, so its gross I is used as published.Which way up
x-x; laid flat they move in to
the y-y axis and Z falls with them. Flat is drawn web-up, so the
containment lands on a flat face and the flanges hang as legs.| ambient, 165 N/mm2 | fire, BS 8519 Table E.1 | |||||
|---|---|---|---|---|---|---|
| Span m | Fmax kN | L/200 kN | L/360 kN | 30 min kN | 1 h kN | 2 h kN |
| 0.25 | 102.960 | 958.648 | 532.582 | 5.616 | 5.616 | 3.744 |
| 0.50 | 51.480 | 239.662 | 133.146 | 2.808 | 2.808 | 1.872 |
| 0.75 | 34.320 | 106.516 | 59.176 | 1.872 | 1.872 | 1.248 |
| 1.00 | 25.740 | 59.916 | 33.286 | 1.404 | 1.404 | 0.936 |
| 1.25 | 20.592 | 38.346 | 21.303 | 1.123 | 1.123 | 0.749 |
| 1.50 | 17.160 | 26.629 | 14.794 | 0.936 | 0.936 | 0.624 |
| 1.75 | 14.709 | 19.564 | 10.869 | 0.802 | 0.802 | 0.535 |
| 2.00 | 12.870 | 14.979 | 8.322 | 0.702 | 0.702 | 0.468 |
| 2.25 | 11.440 | 11.835 | 6.575 | 0.624 | 0.624 | 0.416 |
| 2.50 | 10.296 | 9.586 | 5.326 | 0.562 | 0.562 | 0.374 |
| 2.75 | 9.360 | 7.923 | 4.402 | 0.511 | 0.511 | 0.340 |
| 3.00 | 8.580 | 6.657 | 3.698 | 0.468 | 0.468 | 0.312 |
8σZ/L at σ = 165 N/mm² ambient and BS 8519 Table E.1 in fire; 384EI/(5rL²) for deflection. Properties BS 4-1 not in the Blue Book. Assumes the compression flange is restrained — see below.| ambient, 165 N/mm2 | fire, BS 8519 Table E.1 | |||||
|---|---|---|---|---|---|---|
| Span m | Fmax kN | L/200 kN | L/360 kN | 30 min kN | 1 h kN | 2 h kN |
| 0.25 | 21.595 | 138.056 | 76.698 | 1.178 | 1.178 | 0.785 |
| 0.50 | 10.798 | 34.514 | 19.174 | 0.589 | 0.589 | 0.393 |
| 0.75 | 7.198 | 15.340 | 8.522 | 0.393 | 0.393 | 0.262 |
| 1.00 | 5.399 | 8.628 | 4.794 | 0.294 | 0.294 | 0.196 |
| 1.25 | 4.319 | 5.522 | 3.068 | 0.236 | 0.236 | 0.157 |
| 1.50 | 3.599 | 3.835 | 2.130 | 0.196 | 0.196 | 0.131 |
| 1.75 | 3.085 | 2.817 | 1.565 | 0.168 | 0.168 | 0.112 |
| 2.00 | 2.699 | 2.157 | 1.198 | 0.147 | 0.147 | 0.098 |
| 2.25 | 2.399 | 1.704 | 0.947 | 0.131 | 0.131 | 0.087 |
| 2.50 | 2.160 | 1.381 | 0.767 | 0.118 | 0.118 | 0.079 |
| 2.75 | 1.963 | 1.141 | 0.634 | 0.107 | 0.107 | 0.071 |
| 3.00 | 1.800 | 0.959 | 0.533 | 0.098 | 0.098 | 0.065 |
Zy. Properties BS 4-1 not in the Blue Book. No lateral-torsional buckling to check this way up.| ambient, 165 N/mm2 | fire, BS 8519 Table E.1 | |||||
|---|---|---|---|---|---|---|
| Span m | Fmax kN | L/200 kN | L/360 kN | 30 min kN | 1 h kN | 2 h kN |
| 0.25 | 219.120 | 2683.699 | 1490.944 | 11.952 | 11.952 | 7.968 |
| 0.50 | 109.560 | 670.925 | 372.736 | 5.976 | 5.976 | 3.984 |
| 0.75 | 73.040 | 298.189 | 165.660 | 3.984 | 3.984 | 2.656 |
| 1.00 | 54.780 | 167.731 | 93.184 | 2.988 | 2.988 | 1.992 |
| 1.25 | 43.824 | 107.348 | 59.638 | 2.390 | 2.390 | 1.594 |
| 1.50 | 36.520 | 74.547 | 41.415 | 1.992 | 1.992 | 1.328 |
| 1.75 | 31.303 | 54.769 | 30.427 | 1.707 | 1.707 | 1.138 |
| 2.00 | 27.390 | 41.933 | 23.296 | 1.494 | 1.494 | 0.996 |
| 2.25 | 24.347 | 33.132 | 18.407 | 1.328 | 1.328 | 0.885 |
| 2.50 | 21.912 | 26.837 | 14.909 | 1.195 | 1.195 | 0.797 |
| 2.75 | 19.920 | 22.179 | 12.322 | 1.087 | 1.087 | 0.724 |
| 3.00 | 18.260 | 18.637 | 10.354 | 0.996 | 0.996 | 0.664 |
| ambient, 165 N/mm2 | fire, BS 8519 Table E.1 | |||||
|---|---|---|---|---|---|---|
| Span m | Fmax kN | L/200 kN | L/360 kN | 30 min kN | 1 h kN | 2 h kN |
| 0.25 | 52.272 | 416.748 | 231.526 | 2.851 | 2.851 | 1.901 |
| 0.50 | 26.136 | 104.187 | 57.882 | 1.426 | 1.426 | 0.950 |
| 0.75 | 17.424 | 46.305 | 25.725 | 0.950 | 0.950 | 0.634 |
| 1.00 | 13.068 | 26.047 | 14.470 | 0.713 | 0.713 | 0.475 |
| 1.25 | 10.454 | 16.670 | 9.261 | 0.570 | 0.570 | 0.380 |
| 1.50 | 8.712 | 11.576 | 6.431 | 0.475 | 0.475 | 0.317 |
| 1.75 | 7.467 | 8.505 | 4.725 | 0.407 | 0.407 | 0.272 |
| 2.00 | 6.534 | 6.512 | 3.618 | 0.356 | 0.356 | 0.238 |
| 2.25 | 5.808 | 5.145 | 2.858 | 0.317 | 0.317 | 0.211 |
| 2.50 | 5.227 | 4.167 | 2.315 | 0.285 | 0.285 | 0.190 |
| 2.75 | 4.752 | 3.444 | 1.913 | 0.259 | 0.259 | 0.173 |
| 3.00 | 4.356 | 2.894 | 1.608 | 0.238 | 0.238 | 0.158 |
Zy. Properties SCI P363 Blue Book. No lateral-torsional buckling to check this way up.Do not specify one for fire on its ambient strength
The 76 × 38 on edge is more than six times the fire-rated strut at ambient. At two hours that advantage is all but gone.
| moment capacity, ambient | moment capacity, 2 h | |||
|---|---|---|---|---|
| Section | ambient kN.m | vs FR strut | 2 h kN.m | vs FR strut |
| fire-tested strut | 0.5021 | 1.00x | 0.1005 | 1.00x |
| C 76×38 TFC — web vertical | 3.2175 | 6.41x | 0.1170 | 1.16x |
| C 76×38 TFC — laid flat | 0.6748 | 1.34x | 0.0245 | 0.24x |
| PFC 100×50 — web vertical | 6.8475 | 13.64x | 0.2490 | 2.48x |
| PFC 100×50 — laid flat | 1.6335 | 3.25x | 0.0594 | 0.59x |
Three things a published strut table already answers
None of these can be calculated here — the tool does not know where you will drill, how the containment is fixed down, or where the load lands across the flange. So it says each of them on the sheet instead, and warns on the one case it can see.
- Holes. EN 1993-1-1 §6.2.5: a hole in the compression zone needs no allowance where a fastener fills it; one in the tension flange or the web tension zone may only be ignored where the net section still develops the gross yield. On a cantilever the top flange is the tension flange, so a rod hole over the support is not free there. And unlike Unistrut, whose published capacity has its slots already in it, a derived capacity is the gross section — drilling it is a deduction they never had to make.
- Lateral-torsional buckling, web vertical only. The top flange is in compression, and a
compression flange free to move sideways buckles out of plane well before the section reaches
σZ. The tables above assume it is restrained — containment bolted down at roughly 400 mm centres or closer, which is the normal arrangement. Where a bearer plainly has no such restraint (nothing on it, or its load hanging below on rods) the tool raises a warning; the cases in between are the engineer's. Laid flat there is no lateral-torsional buckling at all — bending is already about the weak axis, so there is no weaker axis to buckle into. That is the trade for a fifth of the capacity. - Torsion. A channel's shear centre lies outside its web, so a vertical load applied in the plane of the web also twists it. Unistrut strut is symmetric about its loading plane and has no such term — and every beam check in this tool is a symmetric-beam model. Load through the shear centre, restrain the section against rotation, or check the torsion by hand. It matters most web-vertical with the load out on one flange, and least laid flat bearing on the web.
Threaded rod
A drop rod is checked on the steel that is actually there — the root of the thread, not the bar it was cut from.
| Rod | Minor dia d3 mm | Area mm2 | Weight kg/m | Source |
|---|---|---|---|---|
| M8 | 6.200 | 30.2 | 0.395 | BS 8519 Table E.2 |
| M10 | 7.858 | 48.5 | 0.617 | BS 8519 Table E.2 |
| M12 | 9.516 | 71.1 | 0.888 | BS 8519 Table E.2 |
| M16 | 13.181 | 136.5 | 1.578 | BS 8519 Table E.2 |
| M20 | 16.529 | 214.6 | 2.466 | BS 8519 Table E.2 |
| M24 | — | 324.26 | 3.550 | basic root area VERIFY |
d3 = d − 1.2269P. The two conventions differ by a roughly fixed 0.3 mm on the
diameter rather than a constant ratio, so M24 cannot be extrapolated from the rest.| Condition | Max stress N/mm2 | Where it comes from |
|---|---|---|
| Ambient | 100 | working stress for mild steel assumed — not from a standard |
| 30 min | 9 | BS 8519:2020 Table E.1 |
| 1 h | 9 | BS 8519:2020 Table E.1 |
| 2 h | 6 | BS 8519:2020 Table E.1 |
Fixings into the structure
The last link, and the one most often assumed. Capacities are per fixing at the characteristic (unfactored) load — a published anchor rating already contains its factor of safety, so applying a load factor on top would count it twice.
| capacity per fixing | ||||||
|---|---|---|---|---|---|---|
| Fixing | Suits | ambient kN | 30 min | 1 h | 2 h | Source |
| VN wedge nut (rib deck) | rib deck | 2.1 | 1 | 1 | 0.4 | Lindapter DECKFIREUK24 / BRE P116310 VERIFY |
| FL312 flange clamp | steel beam | 3.1 | — | — | — | Lindapter datasheet, flange 3–23 mm VERIFY |
| Hilti HUS3 40mm | concrete | 1 | 0.5 | 0.5 | 0.4 | Hilti ETA-13/1038 (HUS3 screw anchor, ~40 mm embedment); ambient = Nrec, fire NRd,fi R30/R60/R120 per EN 1992-4 VERIFY |
| P1796 window clamp | steel beam | 1.45 | — | — | — | Unistrut P1796 window beam clamp VERIFY |
| P1796-B window clamp | steel beam | 1.45 | — | — | — | P1796-B (bigger) window clamp VERIFY |
| Drilled hole + nuts | steel beam | the rod itself, at the stress for the condition | Drilled hole through the flange, full nut + washer each side VERIFY | |||
Containment and load factors
Containment weight
Each run contributes its published weight per metre — the containment plus its cables — multiplied by the bracket spacing.
| Product | kg/m | Product | kg/m |
|---|---|---|---|
| Trunking 50x50 | 4.700 | Basket 50mm - Comms | 2.785 |
| Trunking 75x50 | 7.100 | Basket 100mm - Comms | 4.987 |
| Trunking 100x50 | 9.000 | Basket 150mm - Comms | 7.391 |
| Trunking 150x50 | 12.750 | Basket 200mm - Comms | 9.770 |
| Trunking 100x75 | 12.200 | Basket 300mm - Comms | 14.739 |
| Trunking 100x100 | 15.700 | Basket 400mm - Comms | 24.830 |
| Trunking 150x150 | 34.100 | Basket 600mm - Comms | 29.323 |
| Tray 100mm | 8.517 | Basket 50mm - ELI | 4.210 |
| Tray 150mm | 13.750 | Basket 100mm - ELI | 7.026 |
| Tray 225mm | 21.767 | Basket 150mm - ELI | 10.506 |
| Tray 300mm | 31.800 | Basket 200mm - ELI | 13.848 |
| Tray 450mm | 43.533 | Basket 300mm - ELI | 20.781 |
| Tray 600mm | 56.983 | Basket 400mm - ELI | 26.728 |
| Basket 50mm - Fire | 1.532 | Basket 600mm - ELI | 41.859 |
| Basket 100mm - Fire | 2.557 | Ladder 300mm | 36.200 |
| Basket 150mm - Fire | 3.708 | Ladder 450mm | 44.433 |
| Basket 200mm - Fire | 4.910 | Ladder 600mm | 60.767 |
| Basket 300mm - Fire | 7.373 | Ladder 750mm | 77.533 |
| Basket 400mm - Fire | 10.170 | Ladder 900mm | 101.567 |
| Basket 600mm - Fire | 14.667 |
Load factors
| Symbol | Meaning | Default | Basis |
|---|---|---|---|
| load factor | ambient | 1.300 | designer's choice, editable |
| load factor | in fire | 1.000 | fire is the accidental case |
| Lh | bracket spacing along the run | 1.500 m | designer's input |
| L/x | deflection limit | L/200 | typical for services; L/360 selectable |
| g | gravity | 9.81 m/s2 | — |
The checks, one by one
Each check is a demand and a capacity. What follows is where each side of that comes from, and the arithmetic between them.
6.1 · A point load is not a spread load
The catalogue capacity is a uniformly distributed load. Real containment lands on the bracket through one fixing, so it is a point load — and a point load bends the channel harder. Each one is converted to the equivalent UDL that would produce the same bending moment:
W·L/8. Concentrated
at mid-span it is P·L/4 — twice as much. Setting the two equal gives
W_eq = 2P at p = 0.5, which is exactly what 8p(1−p)
returns. Near a support the factor falls away to nothing, because a load sitting over a rod bends
nothing at all.6.2 · Between the rods, and past them
A channel is not one member. Between two rods it sags; where it runs on past the outer rod it hogs about that rod. Those are different actions with different arithmetic, so they are separate checks — and with three rods there are two bays, each checked at its own length.
6.3 · Where the moment capacity comes from
A cantilever needs a moment capacity, and the catalogue publishes loads. But an
Fmax is the total UDL on a simply supported span, so the moment it implies is
Fmax·L/8 — and that product is constant all the way down the column, because it
is the section's own allowable moment:
| Span m | Fmax kN | Fmax x L / 8 kN.m | Against sigma x Z = 0.5022 |
|---|---|---|---|
| 0.25 | 16.069 | 0.50216 | -0.02% |
| 1.00 | 4.012 | 0.50150 | -0.15% |
| 2.00 | 2.001 | 0.50025 | -0.40% |
| 3.00 | 1.334 | 0.50025 | -0.40% |
6.4 · Strength and deflection are different questions
6.5 · How the load divides between the rods
Where the load sits decides what each rod carries. For two rods this is BS 8519's own method — Annex I, Formula I.1 — a moment balance about the first rod:
Annex I stops at two rods, and tells you to even out an uneven load or add a factor for it. Three or four rods are statically indeterminate, so the tool solves them with the three-moment (Clapeyron) equation instead — which returns exactly Annex I's answer when there are two.
Why not just divide by the number of rods. A bare three-rod bracket splits 18.75 / 62.5 / 18.75, not 33/33/33. The middle rod carries more than three times what an even split suggests, because the rods are far stiffer than the channel spanning between them — an M12 at 1 m is about 87 times stiffer axially than the channel is in bending.
6.6 · The rod itself
Straight out of BS 8519 Formula E.1. Where a bracket lifts a rod rather than pulling it — which a one-sided cantilever can do — the rod is reported as a positive magnitude with the word uplift and checked as a strut, never as a negative weight.
6.7 · Load conservation
Not an engineering check but a guard on the arithmetic: the sum of every element's own weight must equal the sum of what arrives at the structure. If they disagree, a load has been lost or double-counted somewhere in the roll-up, and the sheet says so rather than reporting a tidy answer.
Fire
BS 8519 exists because there is no point in a two-hour cable hanging from a bracket that fails in twenty minutes. Every element is checked twice: at ambient with the load factor, and again at its rating with the whole load still hanging.
The fire factor
Compare the fire columns in section 2 and 3 with the ambient strength column and the relationship is exact, on every span and both sections:
| Rating | P1000TFR | P1001TFR | Reads as |
|---|---|---|---|
| 30 min | 0.750 | 0.750 | steel at roughly 510 C |
| 1 h | 0.420 | 0.420 | roughly 620 C |
| 2 h | 0.200 | 0.200 | roughly 720 C |
What was tested, and what was not
Sources and what to verify
- BS 8519:2020 — Annex E (normative): the drop-rod sizing formula, Table E.1 allowable stress in fire, Table E.2 thread details. Annex I (informative): the load share between rods.
- BS 3643-2:2007 — ISO metric thread minor diameters, via Table E.2.
- Atkore Unistrut & Marco catalogue — channel load tables, section properties, the PNP12 channel nut.
- Atkore Unistrut FR Range — independent fire resistance test to BS EN 1363-1:2020.
- Lindapter DECKFIREUK24 / BRE P116310 — VN wedge nut. Hilti ETA-13/1038 — HUS3 screw anchor.
- BS EN 61537 — containment load/span testing. Wind, snow, ice, seismic and thermal forces are excluded from those tests and left to the installation designer.
- IET Guide to Cables and Cable Management §8.4.4–8.4.7 — the load calculation, the drop-rod share and the containment-span check.
What carries a VERIFY mark, and why
A VERIFY value is one that must be confirmed against current manufacturer literature before a calculation is issued. Three kinds appear on this page:
- Indicative catalogue data — correct when transcribed, but editions change. Channel tables, anchor ratings, containment weights.
- The tool's own assumptions — values no document supplies: the ambient rod stress, the strut factors for an uplifted rod, the fraction of a channel nut's capacity assumed usable in fire.
- Read-across — a published figure applied to something it was not measured on. The cantilever in fire is the clearest case, and the sheet says so.
Every calculation counts how many VERIFY values it actually used and prints the number. A calculation with none is not possible; a calculation where you have checked each one is defensible.
This calculator is a design aid for cable-containment support engineering to BS 8519:2020, not a substitute for a structural engineer's assessment. The exported spreadsheet — with its working visible — is the record of calculation. Loading assumptions, fixing capacities and site conditions remain the responsibility of the design engineer.